FLOOR PROTECTION
This heater must have a non-combustible floor protector (UL1618 ember protection) installed beneath it if the
floor is of combustible material.
each side, 1" to the rear of the unit. Under and 2" beyond each side of the cleanout tee if an interior vertical instillation.
Canada: Floor protector should comply with CAN/ULC standards. Needs to extend 18" to the front, 8" beyond each side of
the unit.
K
L
THROUGH THE WALL
INSTALLATION
All manuals and user guides at all-guides.com
Installation
US: Floor protector should be UL listed or equal too, needs to extend 6" to the front, 6" to
L
M
FLOOR PROTECTOR DIMENSIONS
K
Back to Stove
L
Side to Stove
M
Front to Stove
N
Back and Sides to Flue 6" (153mm)
1" (26mm) U.S. (8" (204mm) Can.)
6" (153mm) U.S. (8" (204mm) Can.)
6" (153mm) U.S. (18" (458mm)Can.)
-5-
J
I
INTERIOR VERTICAL
INSTALLATION
N