Télécharger Imprimer la page

Victron energy Skylla-IP65 24/35 Mode D'emploi page 5

Masquer les pouces Voir aussi pour Skylla-IP65 24/35:

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 31
2.2.1. Main battery connection sequence
The Skylla-IP65 is NOT protected against reverse polarity of the main battery.
("+" connected to "-" and "-" connected to "+").
Follow the installation procedure. The warranty expires when the Skylla-IP65 becomes
defective due to reverse polarity.
Disconnect the mains supply before making or breaking connections to the main battery.
1. Disconnect the mains supply.
2. Disconnect battery cables from the battery.
3. Remove the grey cover in the front panel of the charger, enabling access to the terminals.
4. Connect battery cables to the charger:
5. Connect battery cables to the battery:
6. Connect the mains supply.
2.2.2 Main battery disconnection sequence
When disconnecting the battery cables, be very careful not to accidentally short circuit the
battery.
1. Disconnect the mains supply.
2. Disconnect battery cables from the battery.
3. Remove the grey cover in the front panel of the charger, enabling access to the terminals.
4. Disconnect the battery-cables from the charger.
5. Disconnect all other cables like temperature sensor and/or voltage sensor used with this particular battery.
plus (red) to "+BAT1";
minus (black) to "-BAT".
plus (red) to positive pole,
minus (black) to negative pole.
5

Publicité

loading

Ce manuel est également adapté pour:

Skylla-ip65 12/70