Data On Explosion Protection; Electrical Connections - Camille Bauer SINEAX 2I1 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6. Data on explosion protection

Type
Article
Number
84-2I1-11 154 279
84-2I1-12
154 287

7. Electrical connections

A1
+
3
4
1
2
+
E1
Fig. 3.
Type 84-2I1-10
standard version (non-I.S.).
II (2) G resp. II (1) G
Type of
Electrical data acc. to Certificates
protection
Input
L
= 0
i
C
= 0
i
for connection to
certified intrinsically
[EEx ib] IIC
safe circuit with
following maximum
values:
U
= 30 V
i
I
= 100 mA
i
U
= 253 V AC
m
[EEx ia] IIC
resp.
125 V DC
A1
+
3
4
1
2
+
E1
Terminals 1, 2 blue
Fig. 4.
Type 84-2I1-11
intrinsically safe input.
Type examination
Output
certificate
U
= 253 V AC
m
resp.
125 V DC
PTB 98 ATEX 2176
U
= 12,6 V
o
I
= 100 mA
o
P
= 315 mW
o
lin. characteristic
IIC
IIB
L
4 mH
15 mH
o
C
1.15 µF 7.4 µF
o
Terminals 3, 4 blue
A1
+
3
4
2
1
+
E1
Fig. 5.
Type 84-2I1-12
intrinsically safe output.
Mounting
location
Outside
the
hazardous
area
E1 = Input signal
A1 = Output signal
13

Publicité

Table des Matières
loading