Allocation of fuses, phases and slots, Installation and operation
Depending on the PDU version, provide the following pre-fuse:
PDU basic:
EN
Route the PDU connection cable out of the IT rack and connect it to the mains supply.
Connect one connection cable from the Rittal accessories to a free slot on the PDU and the equip-
ment.
Note:
When connecting the equipment, please note the maximum load per PDU slot (C13:
10 A; C19: 16 A; Earthing pin (CEE 7/3): 16 A; BS 1363 (UK): 13 A).
Depending on the PDU version, unused slots can be closed using the C13/C19 covers from the avail-
able accessories (7955.010 and 7955.015).
If installation is not successful: see section 1.1.
6
Technical specifications
6.1
General technical specifications
Technical specifications
Temperature application range
Humidity application range
Protection category
Protection class
Overvoltage category
Degree of contamination
max. operating height
min. operating time
EU conformity
Electrical connection data
Colour coding of the phases/fuse circuits
(3-phase versions only)
Connection cable type
No. of wires
20
3 x 16 A (16 A versions) or 3 x 32 A (32 A versions)
Temperature Operation: +5 °C...+50 °C (at 100% load)
Temperature Storage: -20 °C...+70 °C
10%...95% relative humidity, non-condensing
IP 20 to IEC 60 529
1
II
2
3,000 meters above sea level
100,000 h
Low-Voltage Directive 2014/35/EU
EMC Directive 2014/30/EU
IEC/EN 62368
DK01:
16 A, single-phase (230 V), 50/60 Hz
DK02:
32 A, single-phase (230 V), 50/60 Hz
DK03:
16 A, 3-phase (400 V), 50/60 Hz
DK04:
32 A, 3-phase (400 V), 50/60 Hz
L1: pink
L2: black
L3: white
H05-VV
3/5 (single-phase/3-phase PDU)
Rittal Power distribution unit PDU basic
+5 °C...+60 °C (at 80% load)