Pour concrete flush
Temporary metal concrete cover
to top of box
(Plastic temporary cover removed)
Tape all holes
and seams
FIGURE 1 - Pre-pour configuration without Plastic cover
Applications: Ceramic Tile (See Figures A, B, or C)
Laminate Flooring (See Figures A, B, or C)
Carpet Flooring with Flat Flange (See Figure E)
VCT with Flat Flange (1/8" Min. Thick. See Fig. B)
8
6
Page 2
Pour concrete flush
to top of plastic
temporary cover
Grease plastic cover(s)
after taping
Tape all holes
and seams
FIGURE 2 - Pre-pour configuration with Plastic cover(s)
Applications: VCT or Carpet with Flush Flange (See Fig. D)
Finished Concrete with Flush Flange (See Fig. F)
4
3
2
1
7
5
Table 1
Small Wiring Chamber
Large Wiring Chamber
Catalog No.
Volumes
Volume
CFB45G55E, xxCRE (1) 99 in [1621 cm ]
(1) 105 in [1721 cm ]
4/5 GANG RECESSED STEEL CONCRETE FLOOR BOX FOR
RECTANGULAR COVERS - Installation Instructions
Catalog no.'s CFB45G55E, CFB45G55CRE
CAUTION: RISK OF ELECTRIC SHOCK. Disconnect power before installing or servicing.
NOTICE: For installation by a qualified electrician in accordance with national and local electrical codes, communication
standards, the following instructions, and any instruction included with individual devices.
NOTICE: Ensure data/communications circuits are separated from lighting/power circuits in accordance NEC and CE code
requirements.
Use with 610GTCVRxx, 610GCCVRxx, and 10GAFBCVRxx series rectangular covers.
Use with CFBS1R8CVRxx series round covers when used with the CFB4510GS1R8ADAPTE round cover adapter.
Use with CFBHUB2, 2 in. metallic conduit hubs, CFBHUB125PVC, 1-1/4 in. non-metallic hubs, or CFBHUB200PVC, 2 in.
non-metallic hubs. May be used in place of knockout plates as needed.
CAUTION: PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING. FINISHED FLOOR TYPES CERAMIC TILE, VCT (Vinyl
Composition Tile) FLOORING, CARPET FLOORING, LAMINATE FLOORING, AND FINISHED CONCRETE FLOORING AFFECT THE
INSTALLATION METHOD.
BEFORE CONCRETE POUR, SEE FIGURES 1, 2, 3, A, B, C, D, E, and F
See Figures 1 or 2 for configuration of concrete covers. For installation applications of FLUSH or FLAT flange styles, see Figs.
A, B, C, D, E and F.
1.
Remove and retain four #8-32 flat head screws [1] from top four corners of the box.
2.
Remove top mounting flange [2] with temporary concrete cover [3] and plastic Cover [4] from box.
3.
Install leveling screws [5] as shown in Figure 3. Level box as required. Be sure to set height of the top of box or temporary
plastic cover to be flush with the finished level of the concrete pour.
4.
Make conduit connections in accordance with application and applicable electric codes. 2" trade size conduit hubs,
(CFBHUB2) or PVC conduit hubs (CFBHUB125PVC, CFBHUB200PVC) may be used in place of knockout plates [6] as needed.
5.
For same side feed-thru wiring, remove non-metallic low voltage divider [7] as necessary.
6.
Re-install top mounting flange [2] with temporary cover [3] and plastic Cover [4] using screws [1] removed in step 1.
(NOTICE: plastic Cover [4] is optional for certain floor applications, see Figures A - E for desired floor application).
7.
Use tape or other to seal all seams and openings outside of box. See Figures 1 and 2.
8.
Pour concrete flush to the top mounting plate [2] or plastic cover [4] as needed.
CFBHUB2
Conduit Hub
2 in. trade size
(sold separately)
Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD-3013
3/23
CFBHUB125PVC
PVC Conduit Hub
1-1/4 in. trade size
(sold separately)
5-1/2"
6"
CFB45G55E
Page 1
ENGLISH

Publicité

loading

Sommaire des Matières pour Hubbell CFB45G55E

  • Page 1 Table 1 40 Waterview Dr. Small Wiring Chamber Large Wiring Chamber Shelton, CT 06484 Catalog No. Volumes Volume 1-800-288-6000 Page 2 www.hubbell-wiring.com CFB45G55E, xxCRE (1) 99 in [1621 cm ] (1) 105 in [1721 cm ] Page 1 PD-3013 3/23...
  • Page 2 Finished Concrete Conc. over Box Pour Depth Flush Cover Ceramic Tile Floor Box Floor Box Pour Depth Flush Flange Cover CFB45G55E, xxCRE 1/2" 6" 610GTCVRxx Page 4 Page 3 CFB45G55E, xxCRE 5-1/2" CFB45G55E, xxCRE 1" ** 610GTCVRxx 6-1/2" ** 610GTCVRxx...
  • Page 3 40 Waterview Dr. Volume canalisation de Volume canalisation de Shelton, CT 06484 Catalog No. c blage (petite) c blage (grande) 1-800-288-6000 Page 2 www.hubbell-wiring.com CFB45G55E, xxCRE (1) 99 in [1621 cm ] (1) 105 in [1721 cm ] Page 1 PD-3013 3/23...
  • Page 4 Fixer le couvercle de la bo te de plancher pour terminer l'assemblage en suivant les directives livr es avec le couvercle. rebord plat de la coul e de la coul e rebord affleurant CFB45G55E, xxCRE 3" 610GCCVRxx CFB45G55E, xxCRE 3-1/2" 610GTCVRxx FIGURE B - Montage du rebord plat - SURFACE (illustr ): FIGURE E - Montage du rebord plat sur la moquette - SURFACE (illustr ): Ajuster le rebord plat au niveau de la surface du carrelage.
  • Page 5 Wiring Device - Kellems HUBBELL M XICO garantiza este producto, de estar libre de defectos en materiales y mano de obra por un a o a partir de su compra. Hubbell reparar o reemplazar el art culo Hubbell Incorporated (Delaware) a su juicio en un plazo de 60 d as.
  • Page 6 Cubierta de brida Caja de piso Profundidad Cubierta de brida sobre caja vertido al ras Caja de piso de vertido al ras CFB45G55E, xxCRE 1/2" 3-1/2" 610GTCVRxx Page 4 Page 3 CFB45G55E, xxCRE 3" 610GTCVRxx CFB45G55E, xxCRE 1" ** 610GTCVRxx 4" **...

Ce manuel est également adapté pour:

Cfb45g55cre