LoRaWAN PULSE - Mode d'emploi / User guide version V1.6.1
1.4.5 Meter compatibility
Examples of meters tested by Adeunis RF (non-exhaustive list)
Type
Water
Gas
Electricity
Heat
2. Preparation and configuration
2.1. Disassembling the casing
The product is delivered disassembled so that you can access the lower part of the electronics. This part enables the sensor or PULSE to be
connected to the screw terminals as well as access to the configuration switches.
Once assembly of the PULSE has been finalised and the configuration has been carried out, the casing can be closed.
NB: Once the casing is closed, it will no longer be possible to open it without running the risk of voiding the IP67 protection index guarantee.
2.2. Fitting the packing gland seal
Before connecting your sensor's cable strands to the product's screw terminals, you must insert the packing gland's nut and the seal appropriate
for your configuration.
Three types of seals are supplied with the LoRaWAN PULSE unit: For a cable with a diameter of 5 mm, for a cable with a diameter of 3 mm, and
Seal for 1 x 5 mm diam. cable
for two cables with diameters of 2.2 mm.
1 - Your sensor and
2 -Pass the cable
its cable
through the packing
gland nut
Name
Itron Flodis
Wehrle TRK-HYX / ETK-EAX
Sappel-Diehl Aquarius/Altair
Elster BK
Socomec Countis E00
Itron CF Echo II
Seal for 1 x 3 mm diam. cable
3 - Pass the cable
4 - Pass the cable
through the packing
through the LoRaWAN
gland seal
PULSE casing base
Itron Cyble Sensor V2
Wehrle Modularis
Dhiel IZAR Pulse 3 & 4 wires
Fludia FM250E and FM250M
Seal for 2 x 2.2 mm diam. cables
5 - Fit the O-ring
onto the seal of the
casing base
Meter type
Elster IN-Z63
6 - Connect the sen-
sor cable strands to
the screw terminals
Page
29
of 41