USER INSTRUCTIONS
Setting parameters
Activating self-learning (heating operating type only)
When the
symbol appears, activate (ON) or deacti-
vate (OFF) the function using the
Press the MODE key within 30 seconds to confirm the
value set.
Self-learning is used to optimise the advance (max. 2
hours) for activating the heating.
The time-thermostat manages the advance automati-
cally, so as to guarantee the set temperature at the be-
ginning of every period of the programmed profile.
This function is activated in heating, in automatic oper-
ating mode only.
Setting the differential regulation value
When the
symbol appears, set the differential reg-
ulation value using the
Press the MODE key within 30 seconds to confirm the
value set.
This value is differentiated by operation type (heating/
air conditioning) and represents the displacement be-
tween the set point set and the actual activation tem-
perature.
It is recommended to retain the preset values except in
special situations.
34
keys.
keys.