Technical Specifications - Bosch FAP-O 520 Guide D'installation

Masquer les pouces Voir aussi pour FAP-O 520:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 9
FAP-O 520 | FAP-O 520-P | FAP-OC 520 | FAP-OC 520-P
Installation
Notes
-
Carefully cut open the packaging of the detectors with C sensor.
-
Do not remove the protective film from the detector head until installation is finished.
Note the following chapters in the Operation Guide:
-
Planning Notes
-
Programming
-
Maintenance and Service incl. Test Instructions
Inserting color rings (P-Variants)
See Figure 3, Page 4 and Figure 4, Page 5.
1.
The detector front plate (1) is secured with a small snap-fit hook (2) on the three-way guideway. To remove,
insert the enclosed opening tool (3) in the slot (4) above the snap−fit hook, secure it with your thumb, turn the
front plate counterclockwise and lift.
2.
From the selected color, place the color rings (5) on the front plate (1) and put on the detector. Only one
position of the front plate is possible.
3.
Turn the cover clockwise to lock it into place. Ensure the sensor windows lie free.
4.
Insert the selected color ring in the trim ring (6).
Mounting the detector and trim ring
See Figure 4, Page 5 and Figure 5, Page 5.
Use of the FAA-500-RTL exchanger device is recommended for removing and inserting the detectors.
1.
Snap the trim ring into place on the base (7).
2.
Remove the protective film from the detector head.
On startup, a protective film left on the detector by mistake is recognized by the system. The message
O-malfunction will occur.
3.
Press the detector one time gently upwards into the base. The push/push system holds the detector.
Due to the guideways, the detector can only be placed in the base in the correct position.
For high mounting heights: The clearly visible two contact plates (8) in the base are on the same side as the
single guideway (9).
Dismantling the detector and trim ring
1.
Press the detector one time gently upwards into the base. The push/push system releases the detector.
2.
Lift the trim ring by the edge to remove it from the base.
Address setting
See Figure 6, Page 5.
Fit a rotary switch in the required position using a pan head slotted screwdriver.
Address (A)
Operating mode
0 0 0
Loop/stub in LSN improved version mode with automatic addressing
0 0 1 - 2 5 4
Loop/stub/T-taps in LSN improved version mode with manual addressing
CL 0 0
Loop/stub in LSN classic mode (address range: max. 127)
2 5 5 - 2 9 9
Non-permitted address range (error message on fire panel)

Technical Specifications

Input voltage
Current consumption
Indicator output
Minimum installation height
Maximum installation height
Minimum distance to lamps
Permissible operating temperature
Permissible rel. humidity
Permissible air speed
Protection class as per IEC 60529
Weight (without/with packaging)
Bosch Sicherheitssysteme GmbH
15 to 33 V DC
3.25 mA
Open collector connects 0 V over 1.5 kΩ through, max. 15 mA
Out of arm's reach
Minimum installation height recommended by BOSCH: 2.70 m
16 m (heed local guidelines)
50 cm
FAP-O 520(-P): -20 °C to +65 °C
FAP-OC 520(-P): -10 °C to +50 °C
<95 % (non-condensing)
20 m/s
FAP-O 520(-P): IP 53
FAP-OC 520(-P): IP 33
FAP-O 520(-P): 170 g/360 g
FAP-OC 520(-P): 180 g/370 g
en
7
F.01U.002.682 | 3.0 | 2011.06

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Fap-o 520-pFap-oc 520Fap-oc 520-p

Table des Matières