Installation distances
C330G
Move the stove in position and check that the minimum installation
distances given in the diagrams are met. The minimum distance in front
of the stove opening to combustible parts of the building or interior
decoration must be at least 1,4 m. If the appliance will be placed on the
floor it must stand on a constructional hearth which meet the building
regulations and has minimum dimension as shown in the diagram.
Combustible roof
750
Combustible floor
!
For use in GB and IE only.
Combustible wall
100
150
500
875
* To prevent discolouration of painted non-flammable walls we recommend that the same side distance as to combustible walls is used.
375
Ø150
140
30
45
Air inlet Ø65
100
150
Constructional
Hearth
Always check that the building has enough bearing capacity for the
hearth, stove and chimney.
When top connecting a steel flue please refer to the relevant
manufacturer's installation instructions. Observe the safety distances to
combustible material that steel flues require.
Combustible wall
100
500
875
Fire-retardant wall of
brick or concrete
100**
475
Constructional
Hearth
Fire-retardant wall of
brick or concrete
50*
425
500
Combustible floor
150
Constructional
Hearth