Télécharger Imprimer la page

United States Stove KING KP5522 Manuel D'instructions Et D'utilisation Du Propriétaire page 7

Publicité

INSTALLATION
ATTENTION:
DO NOT VENT UNDER ANY PORCH, DECK,
AWNING, OR IN ANY SEMI ENCLOSED OR
ROOFED AREA. DOING SO MAY RESULT IN
UNPREDICTABLE AIRFLOW AT THE VENT CAP
UNDER CERTAIN CONDITIONS AND CAN AFFECT
THE PERFORMANCE OF YOUR STOVE, AS WELL
AS, OTHER UNFORESEEABLE ISSUES.
SECURING APPLIANCE TO THE FLOOR
Use the designated holes to secure the unit to the floor.
Fresh Air
Intake
WARNING! DO NOT INSTALL IN SLEEPING ROOM.
CAUTION! THE STRUCTURAL INTEGRITY OF THE
MOBILE
HOME/TRANSPORTABLE
FLOOR, WALL, AND CEILING/ROOF MUST BE
MAINTAINED.
WHEN
INSTALLED
TRANSPORTABLE BUILDING, THE STOVE MUST
BE GROUNDED DIRECTLY TO THE STEEL CHASSIS
AND BOLTED TO THE FLOOR.
In addition to the previously detailed installation
requirements,
mobile
installations must meet the following requirements:
• This stove must be securely fastened to the floor of the
mobile home/transportable building using two 1/4" lag
bolts that are long enough to go through both a hearth
pad, if used, and the floor of the home.
• The heater must be electrically grounded to the steel
chassis of the mobile home/transportable building
with 8 GA copper wire using a serrated or star washer
to penetrate paint or protective coating to ensure
grounding.
• Vent must be 3 or 4-inch "PL" Vent and must extend
a minimum or 36" (914 mm) above the roof line of
Exhaust
Pipe
BUILDING
IN
A
MOBILE
HOME/
home/transportable
building
the mobile home/transportable building and must be
installed using a certified ceiling fire stop and rain cap.
• When
moving
your
building, all exterior venting must be removed while the
mobile home/transportable building is being relocated.
After relocation, all venting must be reinstalled and
securely fastened.
• Outside Air is mandatory for mobile home/transportable
building installation. See Outside Air Supply section
and your dealer for purchasing.
• Check with your local building officials as other codes
may apply.
VENTING REQUIREMENTS
• INSTALL VENT AT CLEARANCES SPECIFIED BY
THE VENT MANUFACTURER.
• DO NOT CONNECT THE PELLET VENT TO A VENT
SERVING ANY OTHER APPLIANCE OR STOVE.
• DO NOT INSTALL A FLUE DAMPER IN THE
EXHAUST VENTING SYSTEM OF THIS UNIT.
The following installation guidelines must be followed
to ensure conformity with both the safety listing of this
stove and to local building codes. Do not use makeshift
methods or compromise in the installation.
THIS UNIT IS EQUIPPED WITH A NEGATIVE DRAFT
SYSTEM THAT PULLS AIR THROUGH THE BURN
POT AND PUSHES THE EXHAUST OUT OF THE
DWELLING. IF THIS UNIT IS CONNECTED TO A FLUE
SYSTEM OTHER THAN THE WAY EXPLAINED IN
THIS MANUAL, IT WILL NOT FUNCTION PROPERLY.
MAXIMUM VENTING DISTANCE
Installation MUST include at least 3-feet of vertical pipe
outside the home. This will create some natural draft to
reduce the possibility of smoke or odor during appliance
shutdown and keep exhaust from causing a nuisance or
hazard by exposing people or shrubs to high temperatures.
The maximum recommend vertical venting height is 12-
feet for 3-inch type "PL" vent. Total length of horizontal
vent must not exceed 4-feet. This could cause back
pressure. Use no more than 180 degrees of elbows (two
90-degree elbows, or two 45-degree and one 90-degree
elbow, etc.) to maintain adequate draft.
7
© 2023 United States Stove Company
mobile
home/transportable
WARNING:
IMPORTANT:

Publicité

loading