► SELF-EJECTING DEVICES
The automatic ejection function uses modified devices, the active
parts of which are protected against the contact test finger
(IP2X/IPXXB, according to standard IEC/EN 60529). These devices
must not be locked.A device releases the retaining latch when
accidental traction is exerted on the flexible power cable. This
device is activated by means of a tension cord connected either to
the flexible cable. The tension cord has a loop at one end and a
cable tie, for clamping the power cable. A crimping lug allows
looping the other end, once passed through to the releasing device
and cut to the desired length.
• Make sure the tension cord is shorter than the flexible cable.
• Make sure that the ejection system operates correctly,
considering the pulling angle of the cable with respect to the axis of
the device.
• Make sure the ejected devices:
are not likely to harm anyone in the vicinity;
are not likely to be damaged or damage any surrounding
equipment.
• Occasionally check the state of the tension cord, of the cable
clamp and the free motion of the ejection mechanism.
IS 06-2 [DSN] Rev A.1 - 2022-11
23/79
.
,