Télécharger Imprimer la page

S+S Regeltechnik PREMASREG 716 Serie Notice D'instruction page 10

Masquer les pouces Voir aussi pour PREMASREG 716 Serie:

Publicité

Les langues disponibles

Les langues disponibles

G
®
PREMASREG
716x
The electronic PREMASREG
®
monitoring and liquid level detection based on pressure measurement in clean air. The devices with a housing made from impact-resistant
plastic, with cable gland or M12 connector according to DIN EN 61076-2-101 and with metal pressure port nozzles (quick connect optional) are
fitted with one switching output, one continuous output and one backlit display for setting the switching point and displaying the ACTUAL values.
The piezoresistive measuring element guarantees a high degree of reliability and accuracy.
This pressure sensor is used in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale
catering facilities, for filter monitoring and level measurement or for triggering frequency converters. The medium measured is air (non-precipitating),
or other gaseous, non-aggressive, non-combustible media. It has a manual zero point pushbutton and an offset potentiometer for final value correction.
Parameter entry is menu-based and is easy to perform using three buttons with the help of the display.
The delivery includes the connection set ASD-06 (2 m connection hose, two pressure port nipples, screws).
TECHNICAL DATA
Power supply:
Load resistance:
Power consumption:
Output:
Connection type:
Measuring function:
Measuring ranges:
Type of pressure:
Pressure connection:
Medium:
Media temperature:
Accuracy:
Sum of Linearity+hysteresis:
Temp. drift values:
Above-⁄ below-atmospheric pressure: max. ± 10000 Pa
Signal filtering:
Signal hysteresis:
Electrical connection:
Cable connection:
Housing:
Dimensions:
Air humidity:
Protection type:
Standards:
Equipment:
K factor:
Units:
Max. value displayed:
ACCESSORIES
716x pressure sensor and switch is equipped with measuring functions for volume flow, differential pressure, filter
24 V AC ⁄ DC (± 10 %) and 15...36 V DC
R
> 5 kOhm
L
< 1.5 VA ⁄ 24 V DC, < 2.8 VA ⁄ 24 V AC
0 -10 V
1 changeover contact (24 V), 1 A ohmic load
3-wire connection
Volume flow, differential pressure, filter monitoring, fill level (adjustable)
10...100% (adjustable)
differential pressure
equipped as standard with metal connection nozzles for pressure hose Ø 6 mm
(optionally with quick connect made from stainless steel for PVC fabric pressure hose Ø 6 mm)
clean air and non-aggressive, non-combustible gases
–20...+50 °C
Type 7161 (1000 Pa): typically ± 5 Pa
Type 7165 (5000 Pa): typically ± 25 Pa
compared to the calibrated reference device
< ± 1 % of final value (pressure)
± 0.1 % ⁄ °C
switchable 1 s ⁄ 10 s (via DIP switches)
and small value suppression < 1 %
± 1 % or final value (pressure) 10 Pa ⁄ 50 Pa
0.14 - 1.5 mm², via plug-in screw terminal
cable gland, plastic
(M 16 x 1.5; with strain relief, exchangeable, inner diameter 10.4 mm) or
M12 connector (male, 12-pin, A-code) according to DIN EN 61076-2-101
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), cover for display is transparent!
126 x 90 x 50 mm (Tyr 2)
< 95 % r. H., non-precipitating air
IP 65 (according to EN 60 529) in the built-in state
CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU,
according to EN 61326-1, according to EN 61326-2-3
Display with illumination, three-line, cutout approx. 70 x 40 mm (W x H),
for displaying the volume flow, differential pressure, contamination degree or level and
for setting the switchpoint, K factor, measuring range limits and other settings
1 to 3000 (adjustable)
m³ ⁄ s, m³ ⁄ min, m³ ⁄ h, l ⁄ s, l ⁄ min, l ⁄ h, %, cm (adjustable)
999999
see table
10
Rev. 2020 - V27 + ID20 - V12