Master settings
Display
Description
MS1
Master On/Off
MS2
Master Modes: None, Identical, Power
MdL
Power Mode Delta Temperature
MS2: Master Modes
None:
All units are Independent of each other.
Each unit operates using its own setpoint and its own Internal Temperature.
The Master still communicates with the Slave units to gather information in case information needs to be
communicated to the Gateway.
Identical Mode:
All units operate as one single unit.
The Master operates using the Maximum Internal Temperature in the network, and the Slaves follow the
operation of the Master.
In this mode, the client needs to only set the Master setpoints.
If a Slave needs to execute the heating mode, Master/Slave operation is ignored.
If the Master needs to execute the heating mode, the Slaves will keep operating on the Maximum Internal
Temperature of the network.
Power Mode:
All units operate using the Master Setpoints but using their own Internal Temperature.
If any unit Internal Temperature exceeds the Master Control Setpoint + Delta, the Master takes back
control of all the Slaves and operation is changed to Identical Mode.
If all Internal Temperatures fall below the Master Control Setpoint, control is released from the Master and
the Slaves will operate Independently based on their own Internal Temperature whilst using the Master
Setpoints.
If a Slave needs to operate in heating mode, Master/Slave operation is ignored.
If the Master needs to operate in heating mode, the Slaves will keep operating on the Maximum Internal
Temperature of the network.