5
Spare parts list
Position
Designation
A
Bonnet DN 15/20
B
Bonnet DN 25
C
Bonnet DN 32
6
Wiring instruction for KHS components with electrical connection
This list of cables only shows examples of applica-
tions. The exact design of the cables in questions
must be carried out on site by the planner on the
Designation
KHS quarter
turn stop
valve PLUS with
spring reset
servo drive
(24 V)
KHS quarter
turn stop
valve PLUS with
spring reset
servo drive
(230 V)
* Possible cable type for fixed routing,
without mechanical load
** Shielded cable lead
Art.-No.
E012068600020KP
E012068600025KP
E012068600032KP
basis of the ambient conditions (temperature,
frequency, routing type, mechanical load).
Cable cross-section/
Art.-No.
-diameter
[mm²] [mm]
3 x X mm²
(power supply)
68601015-032
2 x 2 x 0,80 mm **
(position feedback)
68605015-032
3 x 1,50 mm²
© www.kemper-group.com – 01.2024 / K410068601001-00 – 21 /60
Max. cable
length
[m]
700 (X=1,50)
+
1000 (X=2,50)
1000
Note!
According to VDE 0815: The specifica-
tion of signal transmission cables with
respect to the diameter is specified
in mm.
Cable
type*
NYM-J
+
J-Y(ST)Y
NYM-J