Make sure that the power usage range displayed on the type plate is not exceeded. Otherwise, the
control unit would issue an error message in operating mode.
• Press OK
• Select the type of the connected pump(s) with the arrow keys and confirm with OK; the 0 System info menu
is displayed – the control unit is now ready for operation.
Maintenance date
If no maintenance date is entered, this will be shown in plain text in the display. A maintenance date is entered
using the menu (see 6.1, Setting the maintenance date).
3.4.2
Function check
Preparation
- Make sure that the wastewater container that the pump(s) will drain can be filled with water in as short a time
as possible.
- In the wastewater container, apply a marking slightly below the filling level at which the alarm should be
triggered.
For the function check, two different test procedures are carried
out.
1. Check of the pump(s)
2. Check of the alarm switch
1. Check of the pump(s)
• Switch on the control unit.
• Switch off the pump temporarily using the manual control. To do
so, actuate the <71>* key; the respective LED flashes and the
pump is switched off.
* In the DUO version, also actuate the <73> key
The control unit independently switches the manual control back
to automatic operation after a short period of time. The pump is
then switched on after the respective filling level is reached. If the
subsequent filling of the wastewater container takes longer than
this period of time, the manual control button(s) must be pressed
again.
• Fill the wastewater container up to the marking.
• Do not continue with manual operation; for this purpose, ensure that the <71> (<73>) key is not pressed
again, the control unit will then switch the pump(s) on again and the wastewater container will be drained*.
* In the DUO version, please ensure that the switching off of the second pump works properly according to
the level of the wastewater.