Télécharger Imprimer la page

Hubbell CFB2GS1R6ADAPTE Instructions D'utilisation page 2

Publicité

Les langues disponibles

Les langues disponibles

6.
Wiring channel [7] can be positioned along either side of box.
7.
Reposition mounting plate [2] aligning short leg with wiring channel (SEE FIGURE 3).
8.
Install adapter [9] on top of the mounting plate assembly [2]. Secure using #8-32 screws [1] removed in step 1.
9.
Cover visible openings and screws that penetrate the floor box with duct tape to prevent concrete from entering the box.
Position the floor box with the temporary cover [10] even with slab level. Use leveling screws [5] and wire to keep the floor
10.
box from moving during concrete pour. See TABLE 1 for applicable minimum depth of pour.
11.
Verify that flat head screws [11] holding the temporary cover [10] are secure. After tightening, cover screw heads with duct
tape.
12.
Pour concrete flush to the top of the temporary cover [10].
11
1
8
6
2
FIGURE
3
Catalog No.
Minimum depth of pour
CFB2G25E, CFB2G25CRE
3.25 inches [82.6 mm]
CFB2G30E, CFB2G30CRE
3.75 inches [95.3 mm]
10
9
2
7
5
7
FIGURE
2
TABLE 1
Wiring channel areas
Compatible cover series
CFBS1R6CVRxx, CFBS1R6FFCVRxx
(1) 0.3895 in [251.3 mm ]
CFBS1R6CVRxx, CFBS1R6FFCVRxx
(1) 0.8610 in [555.5 mm ]
AFTER CONCRETE POUR, SEE FIGURES 4, 5, & 6
13.
Locate floor box, remove three screws [11] and remove temporary concrete cover [10]. CAUTION: Temporary concrete
covers are intended to keep concrete residue from entering box during pour and are not intended to support loads. Replace
with permanent flange/cover immediately after concrete has hardened.
14.
Wiring channel [7] must be removed for feed thru wiring and must be reinstalled in all installations. Wiring channel areas
are given in TABLE 1. Use care not to pinch wiring between the wiring channel and box.
CAUTION: ENERGIZING THE ELECTRICAL SYSTEM WITHOUT THE WIREWAY IN PLACE MAY RESULT IN AN ELECTRICAL SHOCK
HAZARD!
15.
Pull and dress wires. If grounded metallic conduit is used, connect green grounding lead [8] to grounding terminal on
receptacle. For a non-metallic conduit system, pigtail a separate grounding wire to ground both box and receptacle.
16.
Install devices using appropriate floor box mounting plates (FBMPxx), sold separately. Use blank plate (FBMPBNK) where no
device is installed. All devices are to be installed in accordance with manufacturer's instructions.
Orient cover support collar [12] as required by removing and reinstalling screws [13]. Lap joint in collar defines the hinge
17.
location of the cover (SEE FIGURES 3 & 4)
18.
Install finished flooring to within 1/8 inch [3.2 mm] of cover support collar [12]. FOR CERAMIC TILE - DO NOT GROUT
BETWEEN THE SUPPORT COLLAR AND TILE.
LAP JOINT
(HINGE SIDE)
FIGURE
4
12
13
13
12
LAP JOINT
(HINGE SIDE)
FIGURE
5

Publicité

loading