Télécharger Imprimer la page

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

18.
Adjust height of cover support collar flush to just below the finished floor. Cover support collar is adjustable for
finished floors of 0 inches to .25 inches [0.0 - 6.4 mm] thick. Tighten mounting screws [12] to 10 - 15 lbs-in torque
[1.1 - 1.7 N m]. For thicker floor finishes use accessory collars (CFB8RCVRR series), sold separately.
19.
Seal the gap around the cover support collar [11] with a continuous bead of electrical grade type RTV silicone sealant
(SEE FIGURE E).
20.
Use the provided floor gasket or apply a 1/4 inch [6.3 mm] thick continuous bead of electrical grade type RTV silicone
sealant around the perimeter on the underside of the flange [13].
21.
Attach flange [13] to the cover support collar [11] using #8-32 flat head screws [14] provided with the cover. Tighten
to 10 - 15 lbs-in torque [1.1 - 1.7 N m].
14
13
SEAL ALL AROUND
FIGURE
E
CFB4G30RCI 4 GANG RECESSED CAST IRON FLOOR BOX FOR
ROUND COVER Installation Instructions
CAUTION: RISK OF ELECTRICAL SHOCK. Disconnect power before installing or servicing.
NOTICE: For installation by a qualified electrician in accordance with all national and local electrical codes,
communications standards, the following instructions and any instructions included with individual devices.
NOTICE: Insure data/communications circuits are separated from lighting/power circuits in accordance with the NEC
and CE Code requirements.
Use with CFBS1R8CVRxx series round covers.
BEFORE CONCRETE POUR, SEE FIGURE A
1.
Remove four #8-32 pan head screws [1] from
top corners of floor box assembly and retain.
2.
Remove transition [2] and mounting plate [3]
assemblies from box and retain.
3.
Install leveling screws [4] as shown in FIGURE A.
4.
Remove closure plugs [5] as needed to make
conduit connections in accordance with
application and applicable electric codes.
Unused conduit ports should be left covered
with closure plugs [5].
5.
For feed-thru wiring, remove non-metallic
dividers [6] as necessary.
6.
Reinstall transition [2] on top of the mounting
plate assembly [3]. Secure using #8-32 pan
head screws [1] in corners.
7.
Cover visible openings and screws that
penetrate the floor box with tape to prevent
concrete from entering the box.
Position the floor box with the temporary cover
8.
[7] even with slab level. Use leveling screws [4]
and wire to keep the floor box from moving
during concrete pour. Minimum depth of pour
is 4.00 inches [101.6 mm]
9.
Verify that flat head screws [8] holding the
temporary cover [7] are secure. After
tightening, cover screw heads with tape to aid
in removal later.
10.
Pour concrete flush to the top of the temporary
cover [7].
Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD2592
04/14
ENGLISH
8
7
1
2
3
6
5
4
FIGURE
A

Publicité

loading

Sommaire des Matières pour Hubbell CFB4G30RCI

  • Page 1 CFB4G30RCI 4 GANG RECESSED CAST IRON FLOOR BOX FOR Adjust height of cover support collar flush to just below the finished floor. Cover support collar is adjustable for finished floors of 0 inches to .25 inches [0.0 - 6.4 mm] thick. Tighten mounting screws [12] to 10 - 15 lbs-in torque ROUND COVER Installation Instructions [1.1 - 1.7 N m].
  • Page 2 All devices are to be installed in accordance with manufacturer's instructions. FIGURE LAP JOINT (HINGE SIDE) FIGURE TABLE 1 FIGURE Catalog No. Minimum depth of pour Wiring channel areas Compatible cover series CFB4G30RCI 4.00 inches [101.6 mm] (2) 0.4040 in [260.7 mm ] CFBS1R8CVRxx...
  • Page 3 0,0 - 6,4 mm. Serrer les vis [12] servant au montage un POUR COUVERCLE ROND CFB4G30RCI Directives de montage couple de 1,1 - 1,7 Nm. Pour les rev tements de sol plus pais, utiliser les colliers accessoires (CFB8RCVRR) vendus FRAN AIS s par ment.
  • Page 4 FIGURE JOINT DE RECOUVREMENT (C T CHARNI RE) TABLE 1 FIGURE N de catalogue Profondeur de coul e minimale Surface de la canalisation S ries de couvercles compatibles CFB4G30RCI 4.00 inches [101.6 mm] (2) 0.4040 in [260.7 mm ] CFBS1R8CVRxx...
  • Page 5 FIGURA Wiring Device - Kellems HUBBELL DE M XICO garantiza este producto, de estar libre de defectos en materiales y mano de obra por un a o a partir de su compra. Hubbell reparar o reemplazar el Hubbell Incorporated (Delaware) art culo a su juicio en un plazo de 60 d as.