13. Technical Data
Housing GS,GSR,GR,GK:
Housing GD:
Power supply:
Power consumption:
Indications:
Outputs relay:
Ambient temp:
Humidity:
Glands:
Screw terminals:
Accuracy:
Sensor technology:
Response time:
Sensors lifetime:
Max. Overrange:
Applicable standards:
Please Note!
The semi conductive sensors used in the GD/GS/GSR/GR/GK-24/230 range of
products are not gas specific. Care should be taken when installing the equipment to
minimize any cross contamination from other gases or vapors.
For further guidance on specific applications contact us.
This product is intended for use in the industrial area.
Specifications subject to change.
12 / 32
GD/GS/GSR/GR/GK-24/230
Polycarbonate, (PC) IP54
Polycarbonate, (PC) IP21
GD/GS/GSR/GR/GK-24: 12-24V AC/DC
GD/GS/GSR/GR/GK-230: 230V AC, 50/60 Hz
Max 2W
Power/Active and alarm indication on three levels.
Potential free contacts (230V, max 5A) .
-40 °C - + 50 °C (Automatic temperature compensation)
0-95% RH (non-condensing)
4 of M16 membrane glands
2
< 1,5 mm
, fuse < 10A
± 5% of the measurement range
Semi-conductive
30 s
5 years
130%
EN 378, EN 14624, JRA 4068
IS Gx Serie 200728