9.1 INTRODUCTION
Ingersoll Rand Nirvana™ Cycling refrigerated air dryers require little
maintenance. These dryers utilize hermetically sealed compressors
which do not require any lubrication. Fan motors require lubrication at
both oil ports every six months. The condensate drain requires annual
replacement of the service unit.
component inspection and service at regular intervals to obtain
maximum performance from your dryer.
9.3 CONDENSATE DISCHARGE SYSTEM
1
2
4
5
6
7
8
9
5
6
8
12
All manuals and user guides at all-guides.com
9.0 SCHEDULED MAINTENANCE
Ingersoll Rand recommends
1
1
2
3
4
10
7
9
9
Nirvana Cycling Refrigerated Dryer Models 2000-2400
http://air.ingersollrand.com
9.2 REFRIGERANT CONDENSER
For standard dryers, regular inspection and cleaning of the condenser
is recommended. Ingersoll Rand dryers may be equipped with an
optional ambient air filter designed to protect the condenser from dirt
and debris that can accumulate on the condenser. For proper operation
with this option, it is imperative that this filter be inspected and cleaned
on a regular basis. Annual replacement of the filter is recommended.
For applications where excessive dirt, dust or debris is encountered,
more frequent inspection and cleaning may be required.
Before drain maintenance work always close the drain isolation
ball valve and ensure that the device is:
• pressureless and
• de-energized.
Maintenance recommendations
Replace service unit (5) annually.
1
Remove control unit (1) by pressing latching hook (2).
2
Detach Drain from outlet (3).
3
Remove design shell (4) (where applicable) using a
screw driver (10).
Remove service unit (5) from pipe at inlet by undoing
union nut
4
or by undoing screws (6) at elbow connector (7)
5
or
by undoing screws (8) at intermediate adapter (9)
6
which is then detached from the service unit by
downward movement.
3
7
• Check if new service unit (5) matches control unit (1)
- type designation and colour of latching hook (2)
• Fit new service unit (5) in reverse order
• Open drain isolation ball valve. Press drain test button to verify proper
drain operation.