GB
6.
FIELD-PROGRAMMABLE SETTINGS
DISPLAY/PRESSURE READINGS
The actual outlet pressure is displayed during normal operation. See „Parameters/Display" section.
Other displays:
Hnd indicates that the Manual mode has been selected.
SOF Internal error of pressure control. Replace valve or contact our Product Support.
Err
Internal overflow.
AEr
Autozero overflow. Contact our Product Support.
PUSHBUTTONS
To enter the Manual mode, press and hold both pushbuttons simultaneously during power up. "Hnd" appears in the display.
Use the UP button to increase the outlet pressure and the DOWN button to decrease it. The actual outlet pressure is
displayed.
Quick presses on the buttons allow you to make slight changes in the pressure rating.
Longer presses allow you to make quick pressure changes.
Press both pushbuttons simultaneously to exit the manual mode.
7.
TECHNICAL CHARACTERISTICS
CONSTRUCTION
Directly operated valve
Body: Aluminium
Internal parts: POM
Seals: Perbunan (NBR), Fluorelastomer (FKM)
Degree of protection: IP65
7.1
FLUID CHARACTERISTICS
FLUIDS
PORTS
MAX. INLET PRESSURE
TEMPERATURE / FLUID
TEMPERATURE / AMBIENT
HYSTERESIS
LINEARITY
REPEATABILITY
MINIMUM SETPOINT
MINIMUM OUTLET PRESSURE
7.2
SPECIFICATIONS
Nominal
Supply voltage
diameter DN
(stabilised) *
(mm)
4
24V DC
+15%/-10%
8
*
Residual ripple: 10 %
Test conditions according to ISO 8778: temperature: 20 °C, relative inlet pressure: 6 bar, relative outlet pressure: 5 bar
Setpoint input
: 0 ... 10 V (100 kOhm input resistance)
0 ... 20 mA / 4 ... 20 mA (250 Ohm input resistance)
Feedback output
: 0 ... 10 V (max. 10 mA), short-circuit protected
0 ... 20 mA / 4 ... 20 mA (max. 24 VDC)
Digital output
: pnp; open collector; max. 200 mA/4.8W, short-circuit protected
HIGH (24 VDC) if feedback=setpoint
LOW (open) if feedback≠setpoint
Overvoltage
: Shut-off at a voltage level higher than 30 volts (+10%).
Low voltage
: Shut-off at a voltage level lower than 19,5 volts (-10 %).
IM14120-10
INSTALLATION
Assembly position: any; for optimum performance vertically with
solenoid at the top.
Air: filtered at 50 µm, free of condensate
Connections: Hemp or Teflon tape must not be used.
Electrical connection: Select a wire section that will give a a volt-
age drop of less than 2 volts at 2A.
: Air or neutral gas, filtered at 50 µm, free of condensate, lubricated or not
: G1/8-G1/4-G3/8, see section 3
: see section 3
: 0...60 °C
: 0...50 °C
: <1% of span
: <0.5% of span
: <0.5% of span
: 100mV (0.2 mA/4.2mA) with shut-off function
: <1% of span
Max.
Max.
power
current
(W)
(mA)
850
21
40
1650
Isolation
Degree of
Kv
class
protection
Nm³/h
0.25
H
IP 65
0.7
INSTALLATION
Flow
Electrical connection
l/min
(SRA)
470
5-pin female
M12 connector
1300