Technical specifications |
Type
RSK-nr
SWH02
672 68 79
SWH12
672 68 89
SWH22
672 68 99
SWH32
672 69 09
SWH33
672 69 19
Type
Air throw*
[m]
SWH02
4
SWH12
8
SWH22
10
SWH32
12
SWH33
11
*1) Applicable at water temperature 80/60 °C, air temperature, in +15 °C.
*2) Applies to fan position 1 – 4.
*3) Conditions: Distance to the unit 5 metres. Directional factor: 2. Equivalent absorption area: 200 m².
*4) ∆t = temperature rise of passing air at maximum heat output and highest airflow.
*5) The air throw data above is valid for highest airflow when the horizontally adjustable air director is used
and the outlet temperature is +40 °C and the room temperature is +18 °C. The air throw is defined as the
distance in a straight angle from the fan heater to the pointwhere the air speed has dropped to 0,2 m/s.
*6) Water volume inside battery.
CE compliant.
Protection class: IPX4.
Fan heater SWH with water heat
Heat output *
Air flow*
1
[kW]
[m³/h]
12
530 - 1120
20
840 - 1810
33
1470 - 3260
51
2870 - 5860
66
2625 - 5420
Water
Voltage
5
volume
[V]
*
6
[l]
1,3
230 V~
1,5
230 V~
2,7
230 V~
3,8
230 V~
5,2
230 V~
SWH
 2
Air flow*
2
[m³/s]
0,15 - 0,31
0,23 - 0,50
0,41 - 0,91
0,80 - 1,63
0,73 - 1,51
Amperage
[A]
0,34
0,64
1,12
2,12
2,13
Sound level
2
*
2,3
[dB(A)]
26 - 39
31 - 48
29 - 55
41 - 58
41 - 58
HxWxD
Weight
[mm]
[kg]
525x515x320
15
600x535x340
19
725x680x370
27
850x820x450
46
850x820x450
46
∆t*
1,4
[°C]
28
22
23
23
31
11