4-6. Weld Output Receptacles And Selecting Cable Sizes
NOTICE − The Total Cable Length in Weld Circuit (see table below) is the combined length of both weld cables. For example, if the power source is
100 ft (30 m) from the workpiece, the total cable length in the weld circuit is 200 ft (2 cables x 100 ft). Use the 200 ft (60 m) column to determine cable
size.
Weld Output
Terminals
!
Turn off power be-
fore connecting to
weld output termi-
nals.
!
Do not use worn,
damaged,
under-
sized,
or
poorly
spliced cables.
Welding
Amperes
+
−
Output Receptacles
This chart is a general guideline and may not suit all applications. If cable overheats, use next size larger cable.
*
**Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.
2
( ) = mm
for metric use
***For distances longer than those shown in this guide, call a factory applications rep. at 920-735-4505 (Miller) or 1-800-332-3281 (Hobart)
Weld Cable Size** and Total Cable (Copper) Length in Weld Circuit