MAGNETIC RING FIXING PROBLEM
If the EN54-16 regulation is necessary, a magnetic ring must be added to the following port lines
1. Network interface (input)
2. Network interface (link)
3. Remote control device interface
4. Control input
5. VELA-FMIC input
6. VELA-MIC input
7. General external control input 1-3
8. Universal external control input 4-6
The following figure shows the cables that must be added with a magnetic loop
VELA-BGM
VELA-AMP
VELA-EXT
1-2 The position of the ring magnet must be placed in the center of the wire and wound once.
3-4 The position of the ring magnet should be near the end of the device, and should be wound once. The
distance between the ports of the ring magnet device should be less than 80 cm.
5-6 The position of the ring magnet should be near one end of the device, and it should be wound once.
The distance between the ports of the ring magnet device should be less than 30 cm.
7
The position of the magnetic ring must be close to the end of the VELA-MFIC, wrapped around, the
distance from the magnetic ring device port must be less than 10 cm, and it must be placed on the
protective cover of the VELA-MFIC.
8
The position of the magentic ring must be placed near the end of the SAIL-MIC, wrapped around it, and
the distance from the port of the ring magnet device must be less than 30cm.
1
5
2
3
3
4
6
6
7
VELA-FMIC
- 2 -
For VELA-MIC the distance
between the magnetic ring
and the devices should be less
than 30 cm
8
VELA-MIC