CAUTION: WHEN INSTALLING, ROUTE FIELD
WIRING AWAY FROM SHARP PROJECTIONS,
CORNERS AND INTERNAL COMPONENTS.
NOTICE: DO NOT USE LOOPED WIRE UNDER
TERMINALS. BREAK WIRE RUN TO PROVIDE
SUPERVISION OF CONNECTION.
*MAX. WIRE DISTANCE (IN FEET) =
* INCLUDES WIRE TO AND FROM APPLIANCE.
ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN (WORST CASE).
CAUTION: APPLIES ONLY TO REGULATED SUPPLIES.
V. MOUNTING ROUGH-IN BOX AND RUN WIRING
MOUNTING - SPEAKER/STROBE
TO GBLP BACK BOX
For use with SSPK24,
SSPKA24, SSPKB24,
SSPKG24 and SSPKR24
Series product.
MOUNTING - OUTDOOR
SPEAKER/STROBE
For use with WSSPK24,
WSSPKA24, WSSPKB24,
WSSPKG24 and WSSPKR24
Series product.
NOTICE: USE FOR WALL
MOUNT APPLICATIONS ONLY.
Adjust power taps using
needle nose pliers.
FOR SSPK24 PRODUCT ONLY
Adjust intensity by inserting small flat blade
screwdriver to turn dial. Displayed number will
indicate selected candela.
NOTICE: FIELD SELECTABLE OPTIONS OF 15, 30,
60, 75 AND 110 CANDELA.
VI. CHECKOUT AND TROUBLESHOOTING
1. Supply power to the system control panel. The auxiliary signaling device should not be activated.
2. If the signal is activated:
a. Check all smoke and fire detectors in the system to make sure they have not been activated.
b. Check all wiring connections to make sure the signal detection circuits are not reversed or shorted together. Check wire color codes and traces.
3. To test the speaker or speaker/strobe product series and other signaling appliances, trip the auxiliary panel, activate alarm circuit at the main control panel or activate one of the fire detection
units in the system. All auxiliary signals should be activated.
4. An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated by local and state codes or authorities having
jurisdiction.
SIGNALING APPLIANCE LIMITATIONS:
Your speaker meets or exceeds current audibility requirements of ANSI/UL 1480. However, if the appliance is located outside a bedroom it may not wake up a sound sleeper, especially if the
room door is closed or only partially open.
THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER. AS FIRES FREQUENTLY CAUSE POWER INTERRUPTIONS,
GENTEX SUGGESTS YOU DISCUSS FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE PROTECTION SPECIALIST.
PANEL VOLTAGE - DEVICE MINIMUM VOLTAGE
TOTAL CURRENT DRAW
FIELD SELECTABLE CANDELA SELECTOR
X WIRE CONDUCTIVITY (STROBE ONLY)
MOUNTING - SPEAKER/STROBE
TO 4" SQUARE x 2 1/8" DEEP
METALLIC BACK BOX
For use with SSPK24,
SSPKA24, SSPKB24,
SSPKG24 and SSPKR24
Series product.
MOUNTING - OUTDOOR SPEAKER
For use with WSSPK
Series product.
NOTICE: USE FOR
WALL MOUNT
APPLICATIONS ONLY.
NOTICE: ALL STROBES ARE DESIGNED TO FLASH
AS SPECIFIED WITH CONTINUOUS APPLIED
VOLTAGE. THIS APPLIANCE IS NOT
RECOMMENDED FOR USE ON CODED OR
PULSING SIGNALING CIRCUITS. HOWEVER, USE
OF THE AVSM CONTROL MODULE IS PERMITTED
TO SYNCHRONIZE THE STROBE.
NOTICE: REFERENCE AVSM CONTROL MODULE
MANUAL (550-0284, DATED 2-1-03) FOR
SYNCHRONIZATION MODULE WIRING DIAGRAMS.
AVSM MANUAL CAN BE OBTAINED AT
HTTP://WWW.GENTEX.COM OR CALL GENTEX
CORPORATION AT 1-800-436-8391.
550-0014
Page 3