UNIVERSAL MOUNT LOW PROFILE SPEAKER AND
CEILING MOUNT LOW PROFILE SPEAKER/STROBE
ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGE 4
MODELS
SSPKCLP*................
LOW PROFILE CEILING OR WALL MOUNT SPEAKER WITHOUT STROBE
SSPK24CLP*............
LOW PROFILE CEILING MOUNT SPEAKER WITH SELECTABLE STROBE
SSPKR24C*..............
LOW PROFILE CEILING MOUNT SPEAKER WITH SELECTABLE STROBE AND RED LENS
* Includes one or more of the following designators, P (plain), A (ALERT), R (red) or W (white).
I.
INTRODUCTION
The Gentex SSPKCLP/SSPK24CLP/SSPKR24C is a high quality speaker and speaker/strobe ANSI/UL Listed for fire protective signaling systems. The high intensity strobe utilizes a Xenon flash
tube which generates a high-intensity light visible from all sides. The SSPK24CLP strobe is ANSI/UL Listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired. The
SSPKR24 strobe is ANSI/UL Listed in compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode Emergency and General Signaling.
II. PRODUCT INFORMATION
The SSPKCLP/SSPK24CLP/SSPKR24 Series speaker and speaker/strobe offer a choice of field selectable power taps, 1/8, 1/4, 1/2, 1, 2 and 4 Watts for either 25v or 70.7v audio amplifiers. The
SSPK24CLP speaker/strobe offers the option of a high intensity strobe which complies with ANSI/UL 1971. The SSPKR24 speaker/strobe offers the option of a high intensity strobe which complies
with ANSI/UL 1638.The frequency range of the speakers is 400-4000Hz. All devices are suitable for line supervision. Speaker includes DC blocking capacitor which allows for supervision voltage
of either polarity.
III. LOCATION
This appliance is intended for use in fire alarm systems and is to be installed in accordance with this installation manual, the recommendation of the local authorities having jurisdiction, and other
NFPA Standards that provide standards on notification appliances for protective signaling systems. The Gentex SSPKCLP/SSPK24CLP/SSPKR24 Series is intended for indoor installation only.
This appliance is not listed for outdoor or drip proof applications.
Room Spacing for Ceiling-Mounted Visible Appliances per NFPA 72, 2013 Edition
Maximum Room Size
Meters
Feet
6.10 x 6.10
20 x 20
9.14 x 9.14
30 x 30
13.4 x 13.4
44 x 44
15.2 x 15.2
50 x 50
NA = Not allowable
**Effective Intensity Requirements for Sleeping Area
Distance from Ceiling to Top of Lens
greater than or equal to 24" (610mm)
less than 24" (610mm)
Visual signal must be installed within 16 feet of the pillow when used in a sleeping area.
Visual signal must be in the direct viewing area of the occupant in order to be seen.
Visual signal cannot be seen when objects such as doors, furniture or walls block strobe light.
NOTICE: VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED.
VISUAL SIGNALS MAY NOT BE THE PREFERRED METHOD FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.
NOTICE: THE STROBE LIGHT MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE STROBE
WILL NOT BE EFFECTIVE.
Visual signal should NEVER be relied upon as the primary fire alert for the hearing impaired under these common sense conditions:
a. Sleeping face down on the bedding or pillow
b. Use of sleep medications of any kind
c. Use of alcoholic beverages or recreational drugs
d. Use of eye shades
e. If there are tendencies of deep sleep conditions
f.
If a fire cuts power to AC circuits, the visual signal will not operate
g. If person is not within line of sight of visual signals
Under these and other similar common situations an alternate fire alert method such as a non-hearing impaired attendant is needed. The visual signal only increases the chance
of being alerted to the presence of fire. No system of this type can fully protect the hearing impaired in case of fire.
SSPKCLP & SSPK24CLP SERIES
ANSI/UL AND CAN/ULC COMPLIANT
SSPKR24 SERIES
ANSI/UL AND CAN/ULC COMPLIANT
SSPK24CLP PRODUCT INFORMATION
Minimum Required Light Output (Effective Intensity, Cd; One Light)
Maximum Ceiling Height
10 Foot Ceiling
20 Foot Ceiling
15
30
30
45
75
75
NA
NA
Visible Notification Appliance
Intensity
110 Cd
177 Cd
30 Foot Ceiling
55
75
NA
95
550-0490