WALL MOUNT LOW PROFILE SPEAKER AND SPEAKER/STROBE
ADDITIONAL CAN/ULC LISTED PRODUCT INFORMATION IS FOUND ON PAGE 4
MODELS
SSPK24WLP*. . . . . . . . . . . . . . . . . .
SSPK24-15/75WLP*. . . . . . . . . . . . .
SSPKA24-15/75PW* . . . . . . . . . . . .
SSPKB24-15/75PW* . . . . . . . . . . . .
SSPKG24-15/75PW* . . . . . . . . . . . .
SSPKR24-15/75PW* . . . . . . . . . . . .
WSSPK* . . . . . . . . . . . . . . . . . . . . . .
WSSPK24-15/75W* . . . . . . . . . . . . .
WSSPKA24-15/75PW*. . . . . . . . . . .
WSSPKB24-15/75PW*. . . . . . . . . . .
WSSPKG24-15/75PW*. . . . . . . . . . .
WSSPKR24-15/75PW*. . . . . . . . . . .
* Includes one or more of the following designators: A (ALERT), P (plain - no text), R (red) or W (white)
I.
INTRODUCTION
The Gentex SSPK24WLP and WSSPK Series is a high quality speaker/strobe. The high intensity strobe utilizes a Xenon flash tube that generates a high-intensity flash visible from all angles.
The SSPK24WLP is provided with a turn dial which allows for candela selection at the installation site; 15Cd, 30Cd, 60Cd, 75Cd, or 110Cd. The SSPK24-15/75WLP, SSPKA24-15/75PW,
SSPKB24-15/75PW, SSPKG24-15/75PW, SSPKR24-15/75PW, WSSPK, WSSPK24-15/75W, WSSPKA24-15/75PW, WSSPKB24-15/75PW, WSSPKG24-15/75PW, WSSPKR24-15/75PW are fixed
candela units, available in 15/75 candela intensity only. This appliance is ideal for any occupancy that requires notification appliances per the applicable building or fire code or wherever dependable
alarms are required.
The SSPK24WLP speaker/strobe strobe is listed in compliance with ANSI/UL 1971, Signaling Appliances for the Hearing Impaired (The SSPK24-15/75WLP model with a fixed 15/75 candela strobe
is additionally listed in compliance with ANSI/UL1638). The SSPKA24-15/75PW, SSPKB24-15/75PW, SSPKG24-15/75PW, SSPKR24-15/75PW, WSSPK, WSSPK24-15/75W,
WSSPKA24-15/75PW, WSSPKB24-15/75PW, WSSPKG24-15/75PW, WSSPKR24-15/75PW strobe is listed in compliance with ANSI/UL 1638, Visual Signaling Appliances - Private Mode
Emergency and General Signaling.
II. PRODUCT INFORMATION
The SSPK24WLP Series speaker/strobe offer a choice of field selectable power taps, 1/8, 1/4, 1/2, 1, 2 and 4 Watts for use with either 25VRMS or 70.7VRMS audio amplifiers. The frequency
range of the speakers is 400-4000Hz. All devices are suitable for line supervision. Speaker includes DC blocking capacitor which allows for supervision voltage of either polarity.
III. LOCATION
This appliance is intended for use in fire alarm systems and is to be installed in accordance with this manual, the recommendation of the local authorities having jurisdiction, and other NFPA
documents that provide standards on notification appliances for protective signaling systems. The SSPK24WLP, SSPK24-15/75WLP, SSPKA24-15/75PW, SSPKB24-15/75PW,
SSPKG24-15/75PW, SSPKR24-15/75PW are intended for indoor installations only; this appliance is not listed for outdoor or drip proof applications. The WSSPK, WSSPK24-15/75W,
WSSPKA24-15/75PW, WSSPKB24-15/75PW, WSSPKG24-15/75PW, WSSPKR24-15/75PW are intended for indoor or outdoor installations; this appliance is listed for outdoor or drip proof
applications when used in conjunction with the GBLP back box.
Visual signal must be installed within 16 feet of the pillow when used in a sleeping area.
Visual signal must be in the direct viewing area of the occupant in order to be seen.
Visual signal can not be seen when objects such as doors, furniture or walls block visual signal.
NOTICE: VISUAL SIGNALS FOR THE HEARING IMPAIRED ARE ONLY ONE METHOD OF ALERTING THE HEARING IMPAIRED.
VISUAL SIGNALS MAY NOT BE THE PREFERRED METHOD FOR NOTIFYING ALL HEARING IMPAIRED INDIVIDUALS.
NOTICE: THE VISUAL SIGNAL MUST BE SEEN BY THE SLEEPING PERSON. IF THE PERSON HAS HEAD TURNED OR
OTHERWISE UNABLE TO BE ALERTED BY VISUAL, THE VISUAL SIGNAL WILL NOT BE EFFECTIVE.
Visual Signal should NEVER be relied upon as the primary fire alert for the hearing impaired under these common sense conditions:
a. Sleeping face down on the bedding or pillow
b. Use of sleep medications of any kind
c. Use of alcoholic beverages or recreational drugs
d. Use of eye shades
e. If there are tendencies of deep sleep conditions
f. If a fire cuts power to AC circuits, the visual signal will not operate
g. If person is not within line of sight of visual signals
Under these and other similar common situations an alternate fire alert method such as a non-hearing impaired attendant is needed. The visual signal only increases the chance of being alerted
to the presence of fire. No system of this type can fully protect the hearing impaired in case of fire.
SSPK24WLP SERIES
ANSI/UL AND CAN/ULC COMPLIANT
SSPKA24, SSPKB24, SSPKG24, SSPKR24,
WSSPK, WSSPK24, WSSPKA24, WSSPKB24,
WSSPKG24, WSSPKR24
ANSI/UL AND CAN/ULC COMPLIANT
WALL MOUNT SPEAKER WITH SELECTABLE STROBE
WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE
WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE, AMBER LENS
WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE, BLUE LENS
WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE, GREEN LENS
WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE, RED LENS
OUTDOOR WALL MOUNT SPEAKER WITHOUT STROBE
OUTDOOR WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE
OUTDOOR WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE, AMBER LENS
OUTDOOR WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE, BLUE LENS
OUTDOOR WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE, GREEN LENS
OUTDOOR WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE, RED LENS
SSPK24WLP PRODUCT INFORMATION
550-0014