Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2013 Edition
Maximum Room Size
Minimum Required Light Output ( Effective Intensity, Cd)
Meters
Feet
6.10 x 6.10
20 x 20
8.53 x 8.53
28 x 28
9.14 x 9.14
30 x 30
12.2 x 12.2
40 x 40
13.7 x 13.7
45 x 45
15.2 x 15.2
50 x 50
16.5 x 16.5
54 x 54
16.8 x 16.8
55 x 55
18.3 x 18.3
60 x 60
19.2 x 19.2
63 x 63
20.7 x 20.7
68 x 68
21.3 x 21.3
70 x 70
24.4 x 24.4
80 x 80
27.4 x 27.4
90 x 90
30.5 x 30.5
100 x 100
33.5 x 33.5
110 x 110
36.6 x 36.6
120 x 120
39.6 x 39.6
130 x 130
NA = Not allowable
IV. ELECTRICAL SPECIFICATIONS
CLEAR Lens Strobe Current Ratings
Use with SSPK24WLP Products
Regulated 24VDC Max.
Candela
Operating Current (mA)
15
30
60
75
110
CLEAR Lens Strobe Current Ratings
Fixed 15/75* Candela Strobe
Use with SSPK24-15/75 AND WSSPK24 Products
Regulated 24VDC Max.
Candela
Operating Current (mA)
15/75
SYSTEM CONSIDERATIONS
1. To select the proper wattage input for the speaker, move the jumper to the appropriate pin.
2. Always maintain electrical isolation between speaker and strobe wiring on combination units.
3. Do not exceed 130% of rated speaker voltage. If excessive distortion is heard, check amplifier for signal clipping. If clipping exists, reduce either amplifier input or gain.
4. Four screws are provided, two for securing speaker to the back box and two for aesthetics. The two non-functional screws will be held in place by the pressure fit of the faceplate.
One Light
Four Lights per Room
per Room
(One Light per Wall)
15
30
34
60
75
94
110
115
135
150
177
184
240
304
375
455
540
635
SSPKA24, SSPKB24, SSPKG24, SSPKR24, WSSPK24, WSSPKA24, WSSPKB24,
WSSPKG24 AND WSSPKR24 PRODUCT INFORMATION
Regulated 24VFWR Max.
Operating Current (mA)
78
113
96
135
137
186
180
245
224
313
Regulated 24VFWR Max.
Operating Current (mA)
96
135
Field Selectable Power Tap Selection - Reverberant (dBA @ 10ft.)
Voltage
1/8 Watt
25 Volts
74.6
70.7 Volts
73.7
NA
NA
NA
15
19
30
30
30
30
37
43
60
60
95
Distance from Ceiling to Top of Lens
95
135
greater than or equal to 24"
135
less than 24"
185
Use with SSPKA24, SSPKB24, SSPKG24, SSPKR24, WSSPKA24,
Lens
Color
Amber
Blue
Green
Red
*The SSPK24-15/75, WSSPK24, SSPKA24, SSPKB24, SSPKG24, SSPKR24, WSSPKA24,
WSSPKB24, WSSPKG24 and WSSPKR24 has a fixed candela rating of 15/75 per ANSI/UL 1638.
NOTICE: DC VOLTAGE RANGE LIMITS: 16-33V. FWR VOLTAGE RANGE LIMITS:
16-33V. THIS PRODUCT WAS ONLY TESTED TO THE STATED VOLTAGE RANGE(S); DO NOT
APPLY 80% AND 110% OF THIS RANGE FOR SYSTEM OPERATION.
1/4 Watt
1/2 Watt
1 Watt
77.7
80.5
83.1
76.7
79.6
82.5
**Effective Intensity Requirements for Sleeping Areas
Visible Notification Appliance
Model
SSPKA24/WSSPKA24
SSPKB24/WSSPKB24
SSPKG24/WSSPKG24
SSPKR24/WSSPKR24
WSSPK24
COLORED Lens Strobe Current Ratings
Fixed 15/75* Candela Strobe
WSSPKB24, WSSPKG24 AND WSSPKR24 Products
Regulated 24VDC Max
Regulated 24VFWR Max.
Operating Current (mA)
148
280
360
397
2 Watt
4 Watt
85.6
87.9
85.4
87.9.
Intensity
110cd
177cd
Color Lens
AMBER
BLUE
GREEN
RED
CLEAR
Operating Current (mA)
395
274
479
438
550-0014
Page 2