3RB22 / 3RB24 Motor Protection Device and 3RB29
Current Measurement Module for Potentially Explosive Areas
Safety and Commissioning Instructions
DANGER
!
Hazardous voltage. Will cause death or serious
injury.
Turn off and lock out all power supplying this device
before working on this device. Installation and
maintenance work on this device as well as
decommissioning may only be carried out by an
authorized electrician.
CAUTION
Reliable functioning of the equipment is only ensured with
certified components.
1. General
Notes and standards
Due to the heightened risk in potentially explosive areas, the following notes and
standards have to be observed carefully:
• EN 60079-14 / VDE 0165 for electrical apparatus for explosive gas atmospheres
• EN 60079-17 Electrical installations inspection and maintenance in explosive
atmospheres.
• EN 50495 Safety devices required for the safe functioning of equipment with
respect to explosion risks.
All 3RB22/3RB24 evaluation modules with 3RB29 current measuring module
are approved under device group II, category (2) in area "G" (environments
where there are potentially expolsive gas, vapor, mist and air mixtures) or for
area "D" (environments with combustible dust). 3RB22 / 3RB24 and 3RB29
devices are not designed for use in hazardous areas. When used in potentially
explosive areas, 3RB22 / 3RB24 and 3RB29 devices must be adapted accord-
ing to the respective ignition protection type.
3RB22: PTB 05 ATEX 3022
3RB24: PTB 11 ATEX 3014
3RB22: TÜV 21 UKEX 7027
WARNING
!
All connection, installation and maintenance work must be carried
out by qualified, responsible specialists. Improper behavior can
lead to severe personal injury or property damage.
2. Installation and Commissioning
NOTICE
Please observe the operating instructions (supplied with the
device) / Equipment Manual
• 3RB22 (Article No.: 3ZX1012-0RB22-1AA1)
• 3RB29 (Article No.: 3ZX1012-0RB00-1AA1)
• 3RB22 / 3RB23 (Article No.: A5W00267534001A)
• 3RB24 (Article No.: 3ZX1012-0RB24-1AA1)
2.1 Setting the motor rated current
Set the 3RB22 / 3RB24 to the rated current of the motor (according to the type
plate or type approval certificate of the motor).
CAUTION
Observe the trip class and the tripping characteristics of the
3RB22 / 3RB24. Select the trip class so that the motor is
thermically protected even when the rotor stalls.
The motor, the lines and the contactors must be designed for the
selected trip class.
4
II (2) G [Ex eb Gb] [Ex db Gb] [Ex pxb Gb]
II (2) D [Ex tb Db] [Ex pxb Db]
II (2) G [Ex eb Gb] [Ex db Gb] [Ex pxb Gb]
II (2) D [Ex tb Db] [Ex pxb Db]
Example: Motor 500 V, 50 / 60 Hz, 110 kW, 156 A, temperature class T3,
T
-time = 18 s, I
/ I
= 5.0
E
A
N
T
=18s
E
I
A
2.2 Thermistor input
Type A temperature sensors with a characteristic curve complying with
EN 60947-8, DIN VDE V 0898-1-401 can be connected to the 3RB22 / 3RB24
evaluation module. Depending on the number of sensors, the following tripping
and re-start temperatures arise:
Typical characteristic curve of a type A sensor
Depending on the number of sensors, the following tripping and re-start tem-
peratures arise in reference to the TNF (rated sensor operating temperature):
Tripping temperature
3 sensors
TNF + 4 K
6 sensors
TNF - 5 K
The temperatures stated are limit values.
NOTICE
The device has automatic thermistor activation. If a thermistor is
connected during the first commissioning, the thermistor evalua-
tion is activated. The thermistor evaluation is not active when
the thermistor LED blinks every 10 seconds!
The configuration test (see "User test") can also be used to check
whether or not the thermistor evaluation has been activated.
3RB22 / 3RB24 / 3RB29
English
Selected switch-off
requirements for the
EEx motor: CLASS 10
/ I
=5,0
N
Re-start temperature
TNF - 7 K
TNF - 20 K
3ZX1012-0RB22-1CA1