BTL7-A/E1 _ 0-M _ _ _ _ -K(8)-SA262-K _ _ /F _ _
Micropulse Transducer - Rod Style
6
Calibration procedure (continued)
6.3.2
Adjusting
The detailed procedure for adjusting is
described on page 16 ff.
The factory set null point and end point is replaced by a
new start point and end point and the associated output
values can be adjusted. The start and end values can be
adjusted as you like up to the limits.
Steps
► Move magnet to the new start position.
► Read new start point by pressing the buttons.
► Set the new start value by pressing the buttons.
New start value
New null point
Fig. 6-4:
Adjust a new start value
14
english
► Move magnet to the new end position.
► Read new end point by pressing the buttons.
► Set the new end value by pressing the buttons.
New end value
Before
Fig. 6-5:
Adjust a new end value
After
6.3.3
Reset
Restoring the transducer to its factory settings.
The detailed procedure for the reset is
described on page 18.
Before
After
New end point