Controller emc1 per unità attuatore Easy-Matic
Formato di comunicazione:
Nella tabella seguente sono elencati tutti i registri utilizzati:
Reg Qty R/W Descrizione
10
5
RO
VAC Firmware Version (Read Only)
100 1
RO
Alarm State. Bit flag of which alarms are current in effect. If an alarm is
active the bit will be Set (1). If an alarm in not active bit will be clear (0).
Several bits can be set at the same time to indicate simultaneous alarms
Bit 0 – Water Detected Alarm
Bit 1 – Over Pressure Alarm
Bit 2 – Over Temperature Alarm
Bit 3 – Flow Detected
101 1
RO
The state of the sensor Connected to Input 1.
High Byte – The type of sensor that is connected.
0 – nothing connected
1 – Water
2 – Over Pressure
4 – Over temperature
8 – Flow Sensor
Low Byte – The current sensor state.
0 – nothing connected
1 – sensor connected, no alarm
3 – sensor connected, alarm
102 1
RO
The state of the Sensor connected to Input 2.
(Description as for
103 1
RO
The state of the Sensor connected to Input 3.
(Description as for 101)
104 1
RO
The state of the Sensor connected to Input 4.
(Description as for 101)
113 5
RO
VAC Serial Number (Read Only)
110 4
RW
Read/Set on board Real Time Clock
Byte 0 – Year (since 2000)
Byte 1 – Month (1-12)
Byte 2 – Day (1-31)
Byte 3 – Hour (00-23)
Byte 4 – Minutes (0-59)
Byte 5 – Seconds (0-59)
Byte 6 – Day of Week (1 = Monday, 7 = Sunday)
Byte 7 – reserved (always 0)
NOTE: The RTC values must be in range when writing new RTC values.
Discrete Inputs (Read Only)
Nella tabella seguente sono elencati i numeri dei «Discrete Inputs» che sono utilizzati per il
controllo dello stato degli allarmi del sensore. Questi sono protetti da scrittura.
Entrata
Descrizione
10
Sensor Alarm. Set if at least one sensor is in alarm.
11
Water Present Alarm. Set if any water sensor is in alarm.
12
Over Pressure Alarm. Set if any over pressure sensor is in alarm.
13
Over Temperature Alarm. Set if any Over Temperature sensor is in alarm.
14
Flow Detected Alarm. Set if any Flow detect sensor is in alarm.