3.3
SNOW CONDITION
To manage the alarm associated with snow, the temperature (NTC 10K/3435K) and the rain sensors must be combined.
ALARM ACTIVATED when
The measured temperature is below 2 °C and
rain has been detected.
3.4
ACTIVATION/DEACTIVATION RAIN SENSOR OR SNOW CONDITION (RAIN+TEMPERATURE)
Sensor deactivation (60 minutes)
Press the "STOP" button of a memorized 7/42
or 3-channel transmitter for 10 s.
The buzzer emits 2 beeps.
3.5
TEMPERATURE SENSOR
The temperature sensor (NTC 10K/3435K) activates whenever there is danger of ice forming.
ALARM ACTIVATED when
The measured temperature is below 2 °C .
What happens with ALARM ACTIVATED
The control unit tilts the slats to 66% of full opening. The control
unit only executes hold-to-run commands.
STOP
(10 s)
What happens with ALARM ACTIVATED
The control unit tilts the pergola slats to 10% of full opening.
L1 flashes
ALARM NOT ACTIVE when
The measured temperature is above 3 °C or rain is
no longer detected. When the control unit receives a
command for automatic movement by transmitter, it
exits the alarm status.
Sensor activation
Press the "STOP" button of a memorized 7/42
or 3-channel transmitter for 10 s. The buzzer
emits a continuous sound.
15
Factory setting
DEACTIVATED
STOP
(10 s)
ALARM NOT ACTIVE when
The measured temperature is above 3 °C or
any command is received
continuous
sound
t
°