Télécharger Imprimer la page

Zoeller 2057 Serie Instructions D'installation page 3

Publicité

Les langues disponibles

Les langues disponibles

STEP 1
INSTALLATION OF THE PUMP IN THE PIT
1.1)
Refer to Figure 1.1 for a typical pump installation.
Figure 1.1
STEP 2
INSTALLATION OF THE VARIABLE LEVEL FLOAT SWITCH
2.1)
Install the float attachment
clamp as shown in Detail A.
IMPORTANT! DO NOT IN-
STALL SWITCH CORD UNDER
HOSE CLAMP
2.2)
Set the pumping range accord-
ing to Chart A and Figure 2.2.
2.3)
Secure the hose clamp to the
discharge pipe.
DETAIL A
4" (10 cm)
MIN.
DETAIL "A"
SK2067A
IMPORTANT! TETHER
LENGTH CANNOT BE
LESS THAN 4" (10 CM).
CHART A
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
1
2
3
4
5
6
7
TETHER LENGTH (INCHES)
MIN. TETHER LENGTH
IMPORTANT! **SECURE THE PUMP POWER CORD TO
THE DISCHARGE PIPE AS SHOWN IN FIGURE 2.2. CORD
SHOULD BE AT OR ABOVE THE PUMP "ON" LEVEL.
© Copyright 2022 Zoeller
PROPERLY GROUNDED CIRCUIT
(GFCI)
CHECK VALVE
VENT PIPE
WEEP HOLE
SECURE CORD
TO PIPE
DISCHARGE
PIPE
PUMP
SK2175
8
9 10 11 12 13 14 15
16
17
(DIMENSION "B")
Co. All rights reserved.
®
3
(typical installation)
COVER
SK2065
Tether "B"
Range "A"
4" (10.2 cm)
6.5" (16.5 cm)
6" (15.2 cm)
8" (20.3 cm)
8" (20.3 cm)
10.5" (26.7 cm)
10" (25.4 cm)
14" (35.6 cm)
12" (30.5 cm)
18" (45.7 cm)
14" (35.6 cm)
22" (55.9 cm)
16" (40.6 cm) 26" (66.0 cm)
Figure 2.2
B
A
"ON"
LEVEL
"OFF"
LEVEL
SK2067B

Publicité

loading

Ce manuel est également adapté pour:

2098 serie2137 serie2282 serie