Temperature Range. Selects the highest temperature in heating mode (18-
− Flow.
EN
EN
FR
Supply temperature (only available in installations with Airzone ZBS 10 KOhm
IT
PT
Information. This parameter provides information about the system and the
DE
If the zone management is selected, the available parameters are:
− Name. Shows the name of the zone.
− Zone ID. Shows the zone number assigned among the available.
− Linked zones. Shows displays the control outputs associated with the
controller.
− Basic mode. The zones can be set in Basic or Advanced mode. They are set in
− User mode setpoint. This option is used to configure the set point temperature
16
30˚C / 64-86˚F, 30˚C / 86˚F by default) and the lowest temperature in cooling
mode (18-26˚C / 64-78˚F, 18˚C / 64˚F by default). It is also possible to disable
some of the modes.
o
Type of opening (only available in installations with intelligent
damper). Use this parameter to configure the type of opening of the
damper output: All/Nothing or Modulating (by default).
o
Minimum air (only available in installations with intelligent damper
and with the parameter Type of opening configured as modulating).
This allows the access of a minimum air flow in zones where the set-
point temperature has been already reached. It is deactivated by
default.
NTC thermistor). This option allows the system demand to be ignored if the
supply temperature exceeds a certain limit. The selectable heating cut out
temperatures are 38-46-54-62-70˚C / 100-114-129-143-158˚F. By default, the
system will stop heating if the supply temperature reaches 54˚C / 129˚F.
Note: The system will not generate heat until past 4 minutes (minimum) from
the shut of demand.
connected elements.
Advanced mode by default. These are the parameters you can control in basic
mode: On/off, set-point temperature, airflow and operation mode.
of each user mode for each zone:
o
Comfort. Heat: 15 to 30˚C / 59 to 86˚F by default 20˚C / 68˚F. Cool: 18
to 30˚C / 64 to 86˚F, by default 24˚C / 75˚F.
o
Eco. Heat: 15 to 30˚C / 59 to 86˚, by default 19˚C / 66˚F. Cool: 18 to
30˚C / 64 to 86˚F, by default 25˚C / 77˚F.
o
Unoccupied. Heat: 15 to 22˚C / 59 to 72˚F, by default 17˚C / 63˚F.
Cool: 24 to 30˚C / 75 to 86˚F, by default 27˚C / 81˚F.
o
Vacation. Heat: 10 to 16˚C / 50 to 61˚F, by default 10˚C / 50˚F. Cool:
29 to 35.5˚C / 84 to 96˚F, by default 35˚C / 95˚F.