Press on "Detect systems to update the server.
If the system management is selected, the available parameters are:
− Name. Shows the name of the system.
− System ID. Shows the number of the system within your installation.
− Global Ventilation. This menu allows you to activate/deactivate the fan mode
EN
in all zones when the system is not actively heating or cooling any zones. By
default, the global ventilation is deactivated. When activated, the following
settings are used to configure Global Ventilation:
EN
FR
IT
− Auxiliary Heat. This menu is used to enable/disable the auxiliary heat. By
default, the auxiliary heat is disabled. When auxiliary heat is enabled, the
PT
following parameters are used to configure the operation of the auxiliary heat:
DE
14
o
Every (min). Configure the length of the interval (in minutes) between
periods of ventilation. Configurable from 5 to 40 minutes, in 5 minutes
increments (by default, 15 minutes).
o
Run For (min). Configure the time duration that ventilation is activated
(in minutes). Configurable from 5 to 20 minutes, in 5 minutes increments
(by default, 10 minutes).
o
Available Stages. Defines how many stages of auxiliary heat a system has.
o
First Supply Heat. If the setting for Auxiliary heat is 1 or 2, then the first
system to supply heat must be defined as either: Heat Pump or Aux. Heat.
o
Fan Configuration. Select between Electric (Fan on) or Furnace (Fan off)
option. If you select Electric option, define:
Fan Delay (s). Defines the delay time (in seconds) to turn on/off
the fan when there is no demand from the Auxiliary Heater.
Possible values are 0, 45, 60 and 120 seconds.
First Stage Menu
- First Stage Differential. Temperature that the system has to
surpass to activate the first stage of auxiliary heat. Values: 1 to 5˚C /
2 to 10˚F in increments of 0.5˚C / 1˚F. By default, 1˚C / 2˚F.
- First Stage Hysteresis. Defines the hysteresis for the operation of
the first stage. Values: 1 to 5˚C / 2 to 10˚F in increments of 0.5˚C / 1˚F.
By default, 1˚C / 2˚F.
- Min. Time Exhausted. Minimum time that the Heat Pump must be
active before the first stage of auxiliary heat can be activated.
Possible values are 0, 45, 60 and 120 minutes. By default, 45 minutes.