SYSTEM

Part 1: General

1 .1 Description
A. The Haier Tempo heat pump air conditioner shall be a variable capacity, mini-split type system comprised of a single
outdoor and a single wall-mounted indoor unit.
1 .2 Toxicity
A. The heat pump system shall participate in RoHS compliance and listed in the directory.

Part 2: Performance and Operating Range

2 .1 Operating Range
A. 1U09TE1VHA, 1U12TE1VHA, 1U09TE2VHA, 1U12TE2VHA, 1U18TE2VHA, 1U24TE2VHA, 1U24TL2HFA, and
1U3036TL2HFA heat pump models shall provide cooling at a temperature range of 23°~115°F (-5°~46°C) without a
wind baffle.
B. 1U09TE1VHA, 1U12TE1VHA, 1U09TE2VHA, 1U12TE2VHA, 1U18TE2VHA and 1U24TE2VHA heat pump models shall
provide cooling at a temperature range of 14°~115°F (-10°~46°C) with a front wind baffle.
C. 1U24TL2HFA and 1U3036TL2HFA heat pump models shall provide cooling at a temperature range of -4°~115°F
(-20°~46°C) with a front wind baffle.
D. 1U24TL2HFA and 1U3036TL2HFA heat pump models shall provide cooling at a temperature range of -40°~115°F
(-40°~46°C) with a front, side and rear wind baffle.
2 .2 Performance
The system shall perform within the specified operating window found on the following table.
A. Cooling performance rating shall be verified following AHRI 210/240 standards of 80°F DB/67°F WB (27°/19°C) indoor
temperature and 95°F DB/75°F WB (35°/24°C) outdoor temperature.
B. Heating performance rating shall be verified following AHRI 210/240 standards of 70°F DB/60°F WB (21°/16°C) indoor
temperature and 47°F DB/43°F WB (8°/6°C) outdoor temperature.