Ashley AP5613 Manuel D'instructions Et D'utilisation Du Propriétaire page 9

Table des Matières

Publicité

INSTALLATION
beside any door or window that opens.
B. Minimum 1-foot (0.3m) clearance above any
door or window that opens.
C. Minimum 3-foot (0.91m) clearance from any
adjacent building.
D. Minimum 7-foot (2.13m) clearance from any
grade when adjacent to public walkways.
E. Minimum 2-foot (0.61m) clearance above any
grass, plants, or other combustible materials.
F. Minimum 3-foot (0.91m) clearance from an
forced air intake of any appliance.
G. Minimum 2-foot (0.61m) clearance below eves
or overhang.
H. Minimum 1-foot (0.3m) clearance horizontally
from combustible wall.
I.
Must be a minimum of 3 foot (0.91m) above the
roof and 2 foot (0.61m) above the highest point
or the roof within 10 feet (3.05m).
THROUGH THE WALL INSTALLATION
(RECOMMENDED INSTALLATION)
TYPICAL THROUGH THE
WALL INSTALLATION
Canadian installations must conform to CAN/
CSA-B365. To vent the unit through the wall,
connect the pipe adapter to the exhaust motor
adapter. If the exhaust adapter is at least 18" (457
mm) above ground level, a straight section of
pellet vent pipe can be used through the wall.
Your heater dealer should be able to provide you
with a kit that will handle most of this installation,
which will include a wall thimble that will allow
the proper clearance through a combustible
wall. Once outside the structure, a 3" (76 mm)
clearance should be maintained from the outside
wall and a clean out tee should be placed on the
pipe with a 90-degree turn away from the house.
At this point, a 3ft (0.91m) (minimum) section of
pipe should be added with a horizontal cap, which
would complete the installation. A support bracket
should be placed just below the termination cap
or one every 4ft (1.22m) to make the system more
stable. If you live in an area that has heavy snowfall,
it is recommended that the installation be taller
than 3ft (0.91m) to get above the snowdrift line.
This same installation can be used if your heater is
below ground level by simply adding the clean-out
section and vertical pipe inside until ground level is
reached. With this installation you have to be aware
of the snowdrift line, dead grass, and leaves. We
recommend a 3ft (0.91m) minimum vertical rise on
the inside or outside of the house. The "through the
wall" installation is the least expensive and simplest
installation. Never terminate the end vent under a
deck, in an alcove, under a window, or between two
windows. We recommend Simpson Dura-Vent® or
Metal-Fab® kits.
THROUGH THE ROOF/CEILING
INSTALLATION
• When venting the heater through the ceiling, the
pipe is connected the same as through the wall,
except the clean-out tee is always on the inside
of the house, and a 3" (76 mm) adapter is added
before the clean-out tee.
• You must use the proper ceiling support
flanges and roof flashing (supplied by the pipe
manufacturer; follow the pipe manufacturer's
directions). It is important to note that if your
vertical run of pipe is more than 12ft (3.7m), the
pellet vent pipe size should be increased to 4" (102
mm) in diameter.
• Do not exceed more than 4ft (1.22m) of pipe on a
horizontal run and use as few elbows as possible. If
an offset is required, it is better to install 45-degree
elbows rather than 90-degree elbows.
9
© 2022 United States Stove Company

Publicité

Table des Matières
loading

Table des Matières