IMPROPER INSTALLATION
The use of other components other than stated
herein could cause bodily harm, heater damage,
and void your warranty. The manufacturer will not
be held responsible for damage caused by the
malfunction of a stove due to improper venting or
installation.

FLOOR PROTECTION

TThis heater must have a non-combustible floor
protector (UL1618 ember protection) installed
beneath it if the floor is of combustible material.
The floor protector should be listed to UL 1618 or
equivalent to type 1 ember floor protection. The
floor protection must extend 6" to the front, 6" on
each side and 1" to the rear of the appliance See
diagram for further information.
A
Back to Stove
B
Side to Stove
C
Front to Stove
D
Back to Flue
© 2022 United States Stove Company
1"
26mm
6"
153 mm
6"
153 mm
2"
51 mm
INSTALLATION
CLEARANCES
Your pellet stove has been tested and listed
for installation in residential, mobile home in
accordance with the clearances given below. For
safety reasons, please adhere to the installation
clearances and restrictions. Any reduction in
clearance to combustibles may only be done by
means approved by a regulatory authority.
E
Side Wall to Stove
Side Wall to PL Vent
F
Pipe
G
Back Wall to Stove
Back Wall to PL Vent
H
Pipe
J
Ceiling to Floor
K
Ceiling to Stove
L
Wall to Stove
Side Wall to PL Vent
M
Pipe
N
Wall to PL Vent Pipe
6
8"
235 mm
10"
254 mm
9.25"
235 mm
3"
76 mm
60"
1524 mm
27.5
699 mm
7-1/2"
191 mm
11-1/4"
286 mm
7-1/2"
191 mm