ASSEMBLY INSTRUCTIONS
13. Screw gas hose and regulator to propane cylinder
(not included). Do not cross-thread.
Use a standard 20 lb. propane cylinder only.
(approximately 12.2 in. / 31cm. in diameter and 17.9 in.
/ 45.5cm high).
Use this heater only with a propane vapor
withdrawal supply system. See chapter 5 of the standard
for storage and handling of liquefied petroleum gas,
ANS/NFPA 58. Your local library or fire department
should have this book. Storage of an appliance indoors
is permissible only if the cylinder is disconnected and
removed from the appliance. A cylinder must be stored
outdoors in a well-ventilated area out of the reach of
children. A disconnected cylinder must have dust caps
tightly installed and must not be stored in a building,
garage or any other enclosed area. The maximum inlet
gas supply pressure: 250 psi /1750 kPa. The minimum
inlet gas supply pressure: 5 psi /35kPa. Manifold
pressure with regulator provided: 11 inch W.C/ 2.74 kPa.
The pressure regulator and hose assembly supplied
with the appliance must be used. The installation must
conform with local codes, or in the absence of local
codes,with national fuel gas code, ANS Z223.1/NFPA54,
natural gas and propane Installation Code, CSA B149.1,
or propane storage and handling code, B149.2.
13