ATTENTION
To meet the IFA W3 certification requirements, you
must install an additional 24 VDC strobe light to
emphasize the alarm status of the FilterControl
panel. It must perform 65 +/- 10 flashes per minute
at a light intensity of 700-1000 cd, in accordance
with standard EN 842:1996+A1:2008.
Fig. 4.3
• Install the FilterControl panel at an appropriate position.
• Open the FilterControl panel with the supplied double-bit
key.
• Put the supplied cable glands in the bottom of the
FilterControl panel;
A: M20 steel
B: M16 black
C: M20 black
D: M16 black pp
X3
1
2
3
4
5
Refer to section 4.6 for the specific connections and
cable specifications
• Connect the FilterControl panel to the filter unit in
accordance with the separately supplied electrical diagram.
0000104050/0
• Connect the FilterControl panel to the mains in accordance
with the separately supplied electrical diagram.
A
B
X3
1
2
3
4
5
6
7
8
0000104050/0
A
B
Fig. 4.3
Electric connection of the FilterControl panel
Parameter setting
In case of PRECO-N (precoat) on CART-D or CART-C filter
cartridges, you must make a jumper setting on the terminal
block to postpone the initial activation of the cleaning system
Fig. 4.4
• If applicable, put a jumper on the terminal block (A).
Use of PRECO-N
(refer to section 4.8)
X3
1
2
3
4
5
6
7
8
A
X3
1
2
3
4
5
A
Fig. 4.4
Terminal block inside FilterControl panel
A
9. To maintain the protective layer of PRECO-N on the filter cartridges, the filter
cleaning system will not be activated during the first 30 running hours of the
fan and within 30 hours after filter replacement.
0000104046/150915/0 MultiDust Bank COMPACT
6
7
8
9 10 11 12 13 14 15 16 17 18 19
C
D
9 10 11 12 13 14 15 16 17 18 19
C
D
Jumper setting
yes
9+10
no
none
9 10 11 12 13 14 15 16 17 18 19
6
7
8
9 10 11 12 13 14 15 16 17 18 19
4.6.2
Fan
To start the fan, the start/stop device receives a 24 VDC signal
from the PLC.
A start/stop device is not included in the scope of
supply. To reduce peak loads on the mains, we
recommend the installation of a star-delta switch, a
frequency inverter or an equivalent to start the fan.
The fan starter must be able to receive a 0-24 VDC
signal from the PLC.
ATTENTION
In case of connection voltage 400V/3ph/50Hz:
The use of a frequency inverter makes the 60 Hz fan
suitable to run on a 50 Hz power grid.
Setting of frequency inverter:
- input voltage: 400V
- output voltage: 230V
- frequency: max. 60Hz
Fig. 4.5
• Disassemble the front panel (A) of the fan housing.
• Connect the fan to the mains in accordance with the
separately supplied electrical diagram, the wiring diagram
on the motor connection block and the identification plate.
• Connect the PTC cable in accordance with the separately
supplied electrical diagram.
• Push the
START/STOP FAN
fan.
• Make sure that the direction of rotation of the motor is
correct (clockwise). An arrow (B) on the motor shows the
correct direction of rotation.
• Push the
START/STOP FAN
• If necessary: change the connection of the phases.
• Install the front panel.
.
9
Fig. 4.5
Electric connection of the fan
4.7
compressed air connection
ATTENTION
The compressed air must be dry and oil-free
according to ISO 8573-3 class 6.
To connect the compressed air, proceed as follows.
button (ref. Fig. 5.1A) to start the
button again to stop the fan.
B
A