INSTALLATION
The control may be mounted in any location provided that
the temperature and humidity of the air in which it is
located will not cause a condensation on the switch parts.
If the ventilating equipment manufacturer has made pro-
visions for, or recommendations for location of this con-
trol, then follow those instructions. If not, the following
suggestions should be observed.
1. The control should be mounted approximately six feet
from the floor, as near as possible to the center of the
ventilated area.
2. Do not locate control on or near an outside wall.
3. Wherever possible, mount on a partitioning wall or on
a post.
WIRING
All wiring should be done in accordance with local and national electrical codes and ordinances.
If the manufacturer of the cooling equipment has supplied
a wiring diagram, follow such recommendations. The
following diagrams show the general use of these con-
trols.
and power supply
SETTING THE CONTROL
CONTROLS WITH A FIXED DIFFERENTIAL
The indicator (B) points to the temperature at which the contacts
open to stop the compressor.
To set the control:
Use a screwdriver in the adjusting slot (A) on the front of the
control to rotate dial until the desired temperature at which
the compressor is to stop is positioned directly under the
indicator (B).
Temperature
control
HOT
To line switch
GND
Hot
Line
N
4. Keep the control as far as possible from undesirable
sources of heat and cold, such as:
a. Windows or doors
b. Direct rays from sun
c. Steam, hot water or cold water pipes
d. Adjoining outside walls.
CAUTION
Do not twist or uncoil the coiled bulb on the
bottom of the control case. Do not attach conduit
through coiled element to bottom of control. In-
stead, run conduit to top of control.
High side
pressure control
(if used)
Type
201
Fan
Motor
2
"B" Fixed
indicator
"A" Adjusting
slot