1606-XLS80E Power Supply Instruction Manual
Parallel Operation
Power Supply A
Fuse
*)
AC
+
-
DC
Power Supply B
*)
Fuse
AC
+
-
DC
Serial Operation
Power Supply A
AC
+
-
DC
Power Supply B
AC
+
-
DC
Earth
Check touch current (earth leakage current)! The total touch current is the sum of
the touch currents of all units. Safety limits – depending on the field of application
- apply for the allowed touch current!
EMC
The device is suitable for applications in industrial environment as well as in residential,
commercial and light industry environment without any restrictions.
For further details see datasheet.
EMC Immunity
EN 61000-6-1, EN 61000-6-2
EMC Emission
EN 61000-3-2, EN 61000-3-3, EN 61000-6-3, EN 61000-6-4,
FCC Part 15 Class B
This device complies with FCC Part 15 rules. Operation is subjected to following two
conditions: (1) this device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
CE mark in conformance with EMC guideline 89/336/EEC and 93/68/EEC and low-voltage directive (LVD) 73/23/EWG.
Terminals and Connections
open
1.
Insert the wire
Physical Dimensions, Indicators and Cooling
Width
32mm / 1.26''
Height
124mm / 4.88''
Depth
102mm / 4.02''
Weight
420g / 0.93lb
Use DIN-rails according to EN 60715 or EN 50022
DIN-Rail
with a height of 7.5 or 15mm
Mounting
Output terminal on top and input terminals on the bottom.
Orientation
For other orientations consult factory.
Indicators
Normal operating mode
®
BonusPower
operation
Overload (V
< 90%)
OUT
Overload (V
< 80%)
OUT
Short-circuit (V
= 0)
OUT
Temperature shut-down
No input power
PU-358.010.38-10A
(1) Power supplies can be paralleled to
increase output power or to build redundant
systems.
(2) For parallel operation use power supplies
of the same family.
(3) Use load connection wires of the same
+
gauge and length.
Load
(4) Set the output voltages of all power
-
supplies to the same value.
(5) A fuse is only required if more than three
units are connected in parallel.
(1) It is possible to connect as many units in
series as needed, providing the sum of the
voltage does not exceed 150Vdc.
(2) For serial operation use power supplies
of the same type.
(3) Grounding of the output is required when
+
the sum of the output voltage exceeds
Load
60Vdc.
-
*)
close
2.
Snap the lever
Plus DIN-rail depth
DC-ok LED
Overload
(green)
lamp (red)
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
Flashing
Flashing
OFF
OFF
Operation on Two Phases
L1
L3
Center
N
Tap
L2
Operation with DC Input
+
Fuse
-
Safety
Separation of output
Touch current
Isolation resistance
PE resistance
Transformer
Approvals
Terminals
Input
Type
Bi-stable, quick-connect spring clamp terminals
Ferrules
Allowed, but not required
Solid wire
0.5-6mm
Stranded wire
0.5-4mm
AWG
AWG 20-10
Stripping length
10mm / 0.4inch
Pull-out force
10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (UL486E)
Use appropriate copper cables that are designed for an operating temperatures of 60°C (for ambient
up to 45°C) and 75°C (for ambient up to 60°C), minimum. Follow national installation codes and
regulations! Ensure that all strands of a stranded wire enter the terminal connection! Up to two
stranded wires with the same cross section are permitted in one connection point (except PE wire). Do
not use without PE (Ground) connection!
Air flow
Do not obstruct air flow! The unit is convection cooled. Ventilation grid must be kept free of any obstructions.
Keep installation clearances at higher ambient temperature and full load:
60mm on top and on the bottom, 15mm on the left and right side
(1) The rated supply voltage must be below
240V.
L
(2) Use an appropriate fuse to protect the N
N
terminal!
Fuse
PE
DC
(1) The power supply will operate with a DC
input voltage.
AC
(2) Use a battery or similar DC source.
+
+
L
(3) Connect +pole to L and –pole to N
Load
N
-
-
(4) In case the –pole of the battery is not
PE
grounded, use an appropriate fuse to protect
DC
the N terminal.
(5) Connect the ground terminal of the power
supply to a PE wire or to machine ground.
SELV
IEC/EN 60950-1
PELV
EN 60204-1, EN 50178, IEC 60364-4-41
max. 0.3 mA
Earth leakages current, TN- mains
min. 5MOhm
Input to output, 500Vdc
max. 0.1Ohm
Between housing and ground terminal
Safety transformer according to IEC/EN 61558-2-17
See datasheet or markings on the unit
Output
2
0.3-4mm
2
0.3-2.5mm
AWG 28-12
6mm / 0.25inch
2
2