VRA and VSA FAILSAFE range
Star drive nut
Code
VRA25.70A.GS2
17 (0.67in) F05/F07
VRA25.70B.GS2
17 (0.67in) F05/F07
VRA45.70A.GS2
17 (0.67in) F05/F07
VRA45.70B.GS2
17 (0.67in) F05/F07
VRA75.70A.GS2
17 (0.67in) F05/F07
VRA75.70B.GS2
17 (0.67in) F05/F07
VSA100.90A.GS2
22 (0.87in) F07/F10
VSA100.90B.GS2
22 (0.87in) F07/F10
VSA150.90A.GS2
22 (0.87in) F07/F10
VSA150.90B.GS2
22 (0.87in) F07/F10
VSA300.90A.GS2
22 (0.87in) F07/F10
VSA300.90B.GS2
22 (0.87in) F07/F10
Please consider 1.5 safety factor (and 2.0 safety factor for POSI version) when sizing the actuator
16
Torque
Connection
25Nm (222in.lbf)
25Nm (222in.lbf)
45Nm (400in.lbf)
45Nm (400in.lbf)
75Nm (665in.lbf)
75Nm (665in.lbf)
100Nm (888in.lbf)
100Nm (888in.lbf)
150Nm (1330in.lbf)
150Nm (1330in.lbf)
300Nm (2660in.lbf)
300Nm (2660in.lbf)
 
Voltage supplies
100V à 240V 50/60Hz (125V à 320V DC)
24V 50/60Hz (24V DC)
100V à 240V 50/60Hz (125V à 320V DC)
24V 50/60Hz (24V DC)
100V à 240V 50/60Hz (125V à 320V DC)
24V 50/60Hz (24V DC)
100V à 240V 50/60Hz (125V à 320V DC)
24V 50/60Hz (24V DC)
100V à 240V 50/60Hz (125V à 320V DC)
24V 50/60Hz (24V DC)
100V à 240V 50/60Hz (125V à 320V DC)
24V 50/60Hz (24V DC)
Power
Operating time
85W
7s
85W
7s
85W
15s
85W
15s
85W
20s
85W
20s
85W
15s
85W
15s
85W
30s
85W
30s
85W
60s
85W
60s