INSTALLATION MANUAL
DGM4D
Smart Card Access Control 4 door controller
E ] ELECTRICAL WIRING DIAGRAM: PUSH BUTTONS
The exit push buttons are connected to the controller terminals at connectors J2, J5, J8 and J11.
Connecting the opening control:
- The door is controlled by dry contact with the relay terminals of the controller
on connectors J1, J4, J7 and J10.
- The lock relay time is set for 5 seconds by default.
- The door timing can be changed from 2 to 20 seconds using the programmer.
- The timing is the same for all the controller (or network of controllers) doors.
This product is delivered with a varistor.
It must be mounted directly on the (electromagnetic lock, motor) strike terminals
controlled by the equipment. The varistor limits the excessive voltage caused by strike
winding – inductance.
F ] ELECTRICAL WIRING DIAGRAM: DOOR SWITCHES
The door switches are connected to the controller terminals at connectors J2, J5, J8 and J11.
They determine if the door is open or closed.
Push Buttons
Ground
J2 ou J5
Door switch
Ground
J2 ou J5
J8 ou J11
J8 ou J11