Valve V3K
Valve V3K-S
(up to 04/2004)
(05/2004 until
with six main
04/2017) with
settings
eight main
settings
2
3
2.5
4
4.5
5
6
Note
W
If there should be any contamination of
the water circuit at a later point in time,
then the valve can be flushed clean at
any time in position 8.
Adjustment diagrams
W
V6K-S adjustment diagram for a system
deviation of 1K (= 0,22 mm stroke) (Fig. 7).
W
V6K-S adjustment diagram for a system
deviation of 2K (= 0,44 mm stroke) (Fig. 8).
W
V3K-F adjustment diagram for a system
deviation of 2K (= 0,44 mm stroke) (Fig. 9).
W
V6K-S allocation table for a system deviati-
on of 1K (= 0,22 mm stroke). Recommen-
ded settings for different radiator outputs
(Fig. 10).
W
V6K-S allocation table for a system devia-
tion of 2K (= 0,44 mm stroke)
(Fig. 11). Recommended settings for diffe-
rent radiator outputs.
Valve V6K-S
(from 04/2017)
with eight main
settings
1
1
2,5
4,5
6
5
8
6,5
Information on
Figure 10 and 11
W
Ф [W]: Heat output of the radiator
W
Δp [mbar]: Pressure loss
W
ΔT: System temperature difference
W
*) Output limit of valve at
version condition: 70/55/20 °C.
Note
W
To roughly determine the setting with the
given radiator output and system tempe-
rature difference, an average differential
pressure of 80 or 100 mbar is recommen-
ded. For systems with great horizontal
expansion, it is necessary to differentiate
the pressure loss: for example 60 mbar
for valves on the most distance radiators,
80 or 100 mbar in the middle area and
120 mbar for valves on radiators near
the centre. This can only be precisely
determined as part of the pipe system
calculation using a suitable computer
program.
5