Connect one phase conductor (normally brown or black)
8
to terminal "L" of the terminal block.
Connect the neutral conductor (normally blue) to terminal
"N" of the terminal block.
Connect the light system phase conductor of the lighting
system to terminal " L " of the terminal block.
Connect the neutral conductor of the lighting system to
terminal "N" of the terminal block.
Connect both the earth (ground) conductor (green/yellow)
of the light system and that of the power cable to the ter-
minal having the earth (ground) symbol.
Configuring the lighting system:
1. Testing Mode
To obtain the test position, turn switch TIME to "T" (Test)
and the switch METER to "+".
When movement is detected in the monitored area, the 4
LEDs and the lamp light for about 2 sec.
2. Settings
Setting the time
Use the TIME potentiometer to set the follow-up time (how
long the light stays lit following the last movement detected).
The range is variable from 6 sec. on the "-" position and 10
min. on the "+" position. Potentiometer turned to its max.
counter-clockwise position is the Test position, potentiometer
turned to its max. clockwise position is a pulse function (1
sec.).
Twilight setting
Use the LUX potentiometer to set the operating threshold of
the Motion Sensor between 5 and ∞ lux. Set the potentiome-
ter to its maximum counter clockwise position " " until twi-
light occurs. This ensures the detector remains inactive during
daylight. When twilight comes, set the desired lux level.
Sensitivity setting
The METER setting allows setting the detector sensitivity as a
function of the distance to the moving object. Turning the po-