USEFUL INFORMATION ABOUT HOW THE HEATING MODE OPERATES
When the incoming water temperature is less than or equal to the required temperature (setpoint
temperature) -X°C, the heat pump will switch to heating mode. The compressor will stop when the
temperature of the incoming water is greater than or equal to the required temperature (setpoint
temperature).
Indicators for adjustment range X and Y
X : adjustable parameter from 1° to 15°C, default setting is 3°C. (Parameter N°6)
STATUS VALUES AND ADVANCED SETTINGS
WARNING
This operation is used to assist servicing and future repairs.
The default settings should only be modified by an experienced professional person.
The system's settings can be checked and adjusted via the remote control by following these steps
1.
Keep pressing
2.
Press
and
3.
Press
to select the setting to be modified.
Note, some settings cannot be modified. Consult the settings table for further information.
4.
Press
and
5.
Press
to set the new value.
6.
Press to
return to the main screen.
Parameter D
4
44
Q_man_SPHP 130 ('21) V6.indd 44
Q_man_SPHP 130 ('21) V6.indd 44
until you enter the settings verification mode.
for see the parameters.
to adjust the setting value.
Value 40
21-12-20 14:15
21-12-20 14:15