WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This control is designed for use on Hot Water Heating systems.
The highly sensitive Hydraulic-Action element is held snugly in
contact with the pipe or tank to provide quick response to
changes in water temperature.
Type 1127 has single-pole, double-throw switch action, offering
terminals that have open-on-rise switch action as well as close-
on-rise switch action. This control may be used as a high limit
control, low limit control, circulator control, or as a combination
low limit and circulator control.
THESE CONTROLS MUST BE INSTALLED BY A QUALIFIED
INSTALLER.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and
ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
This control has been accurately calibrated at the factory. Any
attempt to calibrate this control will void the White-Rodgers
warranty.
If the boiler manufacturer recommends a control location, follow
such recommendations. If none is offered, the following informa-
tion gives suggested locations.
On a domestic heating system, surface mounted controls
may be attached to either a horizontal or a vertical riser approxi-
mately 18 inches above the boiler.
On a unit heater application, they may be attached to the base
of the coil directly in the air path or on the return line.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS RD., ST. LOUIS, MO. 63123
(314) 577-1300, FAX (314) 577-1517
9999 HWY. 48, MARKHAM, ONT. L3P 3J3
(905) 475-4653, FAX (905) 475-4625
TYPE 1127
HOT WATER CONTROL
Surface Type - S.P.D.T.
INSTALLATION INSTRUCTIONS
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.
To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse or
circuit breaker box until installation is complete.
Installation Rules:
1. Remove the insulation on the pipe or tank where the control
is to be mounted.
2. All rough spots, scale, rust, or paint should be removed with
a file or similar tool.
3. Mount the control to the pipe by means of the two clamps
provided. They should be pulled up snugly.
4. Replace the insulation, entirely embedding the shield which
is around the sensitive element of the control.
Printed in U.S.A.
DESCRIPTION
PRECAUTIONS
WARNING
CAUTION
INSTALLATION
PART NO. 37-1209B
Replaces 37-1209 & 37-9122
9547

Publicité

loading

Sommaire des Matières pour Emerson White-Rodgers 1127

  • Page 1 4. Replace the insulation, entirely embedding the shield which is around the sensitive element of the control. WHITE-RODGERS DIVISION PART NO. 37-1209B EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123 Replaces 37-1209 & 37-9122 (314) 577-1300, FAX (314) 577-1517 Printed in U.S.A.
  • Page 2 INSTALLATION CONT. Convenient Installation – May be mounted vertically, horizontally, or on an angle. Will Pipe Insulation Should Cover Shield not affect operation of control. Containing Element. WIRING All wiring should be done according to local and national electrical codes. BLUE OPEN ON RISE Refer to the wiring diagram supplied by the boiler or burner...
  • Page 3 SETTING THE CONTROL CONTROLS WITH FIXED DIFFERENTIAL CONTROLS WITH ADJUSTABLE DIFFERENTIAL The fixed indicator points to the temperature at which the The left-hand indicator points to the temperature at which the contacts open on high limit and low limit applications. On contacts open on high limit and low limit applications.
  • Page 4 à la base du serpentin ou sur la canalisation de retour. WHITE-RODGERS DIVISION PIÈCE No 37-1209A EMERSON ELECTRIC CO. 9797 REAVIS RD., ST. LOUIS, MO. 63123 Remplace 37-1209 & 37-9122 (314) 577-1300, FAX (314) 577-1517 Imprimé aux É.-U.A.
  • Page 5: Installation (Suite)

    INSTALLATION (suite) Installation pratique : La commande peut être montée à la verticale, à l’horizontale ou sur un angle sans que son fonctionnement en soit affecté. L’isolant du tuyau doit recouvrir l’écran qui contient le capteur. CÂBLAGE Tout le câblage doit être conforme aux codes et règlements locaux et nationaux qui régissent les installations électriques. Se référer aux schémas de câblage fournis par le fabricant de BLUE ROUGE...
  • Page 6: Réglage De La Commande

    RÉGLAGE DE LA COMMANDE COMMANDES À DIFFÉRENTIEL RÉGLABLE COMMANDES À DIFFÉRENTIEL FIXE L’indicateur du côté gauche indique la température à laquelle les L’indicateur fixe indique la température à laquelle les contacts contacts seront ouverts lorsque la commande sert de limiteur seront ouverts lorsque la commande sert de limiteur à...