KDP-DALI 01
Presence detector for DALi lighting control
Walk test (Lux setting is inactive)
Thepurposeofconductingwalktestistocheckandadjustdetection
coverage.SetTimeknobto"Test",thenconductingawalktest.
Ittakesapprox.60secfordetectortowarmupafterpowerissupplied,
thendetectorentersintonormaloperationtocarryoutawalktest.
Test procedure
1.
Testermustbewithinthedetectioncoverage.
2.
Switchpoweron.
3.
Ittakesapprox.60secfordetectortowarmupwithloadandredLEDon,
thenturnsoffafterwarminguptime.
4.
WalkfromoutsideacrosstothedetectionpatternuntilredLEDturnson
forapprox.2secthenoff,thenexttriggershouldbe2secinterval
(SeeFIG.13).
5.
Adjustlensshieldfordesireddetectionrange.
6.
Repeatstep4and5untilitmeetsuser'sdemands.
Instructionsmanual|
FIG.12
NOTE
FIG.13
40
www.grupotemper.com