Step 2b: 0-10 V- Wiring
CAUTION - Risk of Fire or Electric Shock. Do
not interconnect the outputs of different Class
2 circuits. Do not tie 0-10 output of device to
EcoSystemR link or another Class 2 source.
Wire per IEC/PELV NECR Class 2 wiring regulations. If
EcoSystemR link is wired per Class 1, the EcoSystemR
wires need to be separated from the 0-10 V- wires by a
barrier or 0.25 in (6 mm) minimum.
1. Use 16 AWG to 18 AWG (1.5 mm² to 1.0 mm²) solid
conductors to wire between the interface and driver.
2. Wire the interface's 0-10 V + terminal (PURPLE) to the
driver's 0-10V + wire (typically purple).
3. Wire the interface's 0-10 V – terminal (GRAY) to the driver's
0-10V – wire (typically gray).
Step 3: Wire Mains to the Interface
Hot and Neutral from a distribution panel are required for
the interface. Verify that the mains voltage matches the
voltage rating of the driver that the interface is controlling.
Use the following guidelines for wiring mains voltage to the
interface.
WARNING - Shock Hazard. To avoid the risk of
electric shock, do not wire live. Interrupt power via
breaker before wiring between the interface and a
driver.
1. Interface terminals only accept solid wire. Join mains input
Hot and Neutral to 16 AWG to 18 AWG (1.5 mm² to 1.0 mm²)
solid wire before connecting to an interface.

Wiring Diagram

Neutral
White
Hot
Black
Purple
E1
E2
Purple/White
EcoSystem
®
Link (E1, E2)
Technical Support: +1.800.523.9466
EcoSystemR to 0-10 V Interface | Install Guide
Neutral
White
Switched Hot
Orange
Ground
EcoSystem
Ground
Neutral
Switched Hot/Out
Constant Hot/In
EcoSystem
®
Digital Link
Wiring within fixture
Wiring between an interface and a driver
Step 3: Wire Mains to the Interface (continued)
2. Wire the Hot input to the HOT (BLACK) terminal on the
interface.
3. Wire the Neutral input to the NEUTRAL (NEU)(WHITE)
terminal on the interface. A pigtail wire is necessary.
4. Wire ground wire to the GROUND (GREEN) ( ) terminal on
the interface.
4. Make sure the driver(s) are correctly wired to the interface
(step 2).
Step 4: Wire EcoSystemR Link
An EcoSystemR link supply controls up to 64 ballasts and
interfaces. EcoSystemR link wiring may be run daisy-chain,
t-tap, and/or star pattern. Link wiring may be either Class
1 or IEC PELV/NECR Class 2.
Class 1: Low voltage link wiring may be run with mains
voltage to any fixture the link is controlling.
IEC PELV/NECR Class 2: Low voltage link wiring must be
separated from all mains and Class 1 wiring by a barrier or
at least 0.25 in (6 mm). Consult all applicable national and
local codes for compliance.
Lutron recommends using two different colors for E1 and
E2 (EcoSystemR link) wire. This helps prevent link wiring
mistakes.
Use the following guidelines for wiring the EcoSystemR link
to the interface.
to 0-10 V
®
Interface
0-10V
Output
+
(bottom view)
Line
In
0-10 V LED Driver
0-10 V
(By Others)
Gray
Purple
To LEDs
Lutron