ATTENTION: Please read this guide before installing
TVI-LMF-2A
120 V~ 50/60 Hz
220/240 V~ 50/60 Hz
277 V~ 50/60 Hz
Overview
The EcoSystemR to 0-10 V Interface provides a control
gateway from an EcoSystemR link to a 0-10 V compatible
lighting device, typically an LED driver.
It allows for individual addressability of the 0-10 V device,
but only provides one-way communication from the controls
to the 0-10 V device. This interface is for single-fixture
control only. For fixtures that have multiple drivers installed
(such as two or three drivers being needed to reach certain
output wattages), only one interface may be necessary. This
interface is not intended for control of multiple fixtures.
System Example
EcoSystemR Link
EcoSystemR
Ballast
IR Receiver
EcoSystemR Master*
(GRAFIK EyeR QS,
QuantumR Hub, etc.)
Lighting Remote
*Does not count as one of the 64 devices allowed on the EcoSystemR link
Technical Support: +1.800.523.9466
EcoSystemR to 0-10 V Interface | Install Guide
TVI-LMF-2A
EcoSystemR
to 0-10 V
Interface
Specifications
Power
• Maximum interface power consumption (at any voltage):
< = 1.0 W when output load is turned on
< = 0.5 W when output load turned off ("standby")
• Relay Output:
2 A of electronic load, 5 drivers maximum
• Input power must be unswitched
0-10 V Control
• Current rating: 25 mA max (sink only)
• Maximum 0-10 V wire length: 10 ft (3 m) from interface
to driver
• Class 1 or IEC/PELV NECR Class 2 wiring allowed,
isolated from line and EcoSystemR link
• Voltage Range:
Off: < = 0.5 V
Minimum light level:
Maximum light level: 10 V
• Compliant to IEC60929 Annex E2 standard ("Control by
DC voltage")
Note:
It is possible to connect more than 1 driver within a fixture
to an interface, with a maximum of 5 drivers. The interface
controls up to 2 A of connected load. If more than one
driver is attached, the drivers are controlled as a single
zone - individual control of multiple attached drivers is not
possible.
0-10 V
EcoSystemR
Driver
Ballast
Keypad
English
1 V
EcoSystemR
LED Driver
Lutron
| 1
®

Publicité

Table des Matières
loading

Sommaire des Matières pour Lutron EcoSystem TVI-LMF-2A

  • Page 1 0-10 V Driver Ballast LED Driver Ballast Interface IR Receiver EcoSystemR Master* (GRAFIK EyeR QS, QuantumR Hub, etc.) Keypad Lighting Remote *Does not count as one of the 64 devices allowed on the EcoSystemR link Technical Support: +1.800.523.9466 Lutron ®...
  • Page 2: Mounting Dimensions

    G 1.99 in (51 mm) L 0.65 in (16.5 mm) Q 0.32 in (8 mm) D 4.90 in (124 mm) H 1.11 in (28 mm) M 0.75 in (19 mm) R 0.29 in (7 mm) 2 | Lutron www.lutron.com/ecosystem ®...
  • Page 3: Wiring Diagram

    Use the following guidelines for wiring mains voltage to the local codes for compliance. interface. Lutron recommends using two different colors for E1 and WARNING - Shock Hazard. To avoid the risk of E2 (EcoSystemR link) wire. This helps prevent link wiring electric shock, do not wire live.
  • Page 4 Interface Warranty Lutron warrants each new interface for a period of three years from the date of shipment, to be free from defects in materials or workmanship under conditions of normal use when installed and operated under Lutron product specifications and in accordance with the applicable National Electrical Code and Safety Standards of Underwriters Laboratories. Lutron shall, at its option, repair or replace any defective unit that, in its opinion, has been properly installed, wired, insulated, used and maintained, provided that Lutron shall not be required to remove, install or re-install any defective unit and provided that Lutron is promptly notified of said defect within the aforementioned warranty period.
  • Page 5: Caractéristiques

    Ballast vers 0-10 V Pilote EcoSystemR EcoSystemR EcoSystemR Interface Récepteur EcoSystemR Master* (GRAFIK EyeR QS, concentrateur QuantumR, etc.) Clavier Télécommande d’éclairage * Ne compte pas comme l’un des 64 appareils autorisés sur la liaison EcoSystemR Assistance technique : +1.800.523.9466 Lutron ®...
  • Page 6: Dimensions De Montage

    G 51 mm (1,99 po) L 16,5 mm (0,65 po) Q 8 mm (0,32 po) D 124 mm (4,90 po) H 28 mm (1,11 po) M 19 mm (0,75 po) R 7 mm (0,29 po) 2 | Lutron www.lutron.com/ecosystem ®...
  • Page 7: Schéma De Câblage

    Utilisez les directives suivantes pour câbler la tension nationaux et locaux applicables. secteur à l’interface. Lutron recommande d’utiliser deux couleurs différentes AVERTISSEMENT - Risque d’électrocution. pour les fils E1 et E2 (liaison EcoSystemR). Cela permet Pour éviter les risques d’électrocution, n’installez d'éviter les erreurs de câblage de la liaison.
  • Page 8: Dépannage

    Garantie de l'interface Lutron garantit pour une période de trois ans à partir de la date de livraison que chaque nouvelle interface est exempte de défauts matériels ou de fabrication dans des conditions normales d’utilisation lorsqu’elle est installée et utilisée selon les caractéristiques des produits de Lutron et conformément au code électrique national applicable et aux normes de sécurité...

Table des Matières